Menu selection
Meaning
Factory setting
START INTERVAL
Minimum time interval between two heat pump starts in minutes.
20M(range:
10M / 30M)
ALARM BRINE
Gives an alarm when the outgoing brine temperature falls below the set value.
(range:
,
-14°C / 10°C)
PRESS. PIPE
Sensor on the compressor’s hot gas line. The value within brackets indicates maximum
permitted temperature. If this value is exceeded, the compressor will stop and start again
as soon as the temperature has dropped. No alarm shown in the display, however, a
square is shown in the left, lower corner of the display.
135°C
OUTDOOR STOP
Displayed only if AIR is selected. Lowest outdoor temperature when the outdoor sensor
stops the compressor and heating or hot water are instead produced by the auxiliary
heater.
-20°C(range:
-20°C / -1°C)
SHUNT TIME
Time in seconds. Indicates how often the shunt is to adjust its opening.
60S(range: 10S /
99S)
SHUNT COOLING
The cooling shunt works towards the set temperature.
18°C(range: 0°C /
30°C)
9.3
Sub-menu AUX. HEATER
Menu selection
Meaning
Factory setting
MAX STEP
Maximum number of permitted steps for auxiliary heating.
= no auxiliary heating per-
mitted (Means that only AUTO or HEAT PUMP can be selected).
2
(range:
, 1, 2,
3, 4, 5, +4, +5)
INTEGRAL A2
Two conditions must be fulfilled in order to start the auxiliary heater: the integral’s value
to start must be less than integral A2, and the supply temperature must be 2°C lower
than the calculated temperature. See
Service Instructions
for more information.
-600(range: -50 /
-990)
HYSTERESIS
If the difference between the actual supply temperature and the calculated supply tem-
perature is too great (see
Service Instructions
for more information), either the integral
value is set to start value A2 (starts the auxiliary heater) or to 0 (stops the auxiliary heat-
er ).
20°C(range: 5°C /
30°C)
MAX CURRENT
Refers to main fuse in the unit, in amperes.
20A(range: 16A /
35A)
HOT WATER STOP
Stop temperature for hot water during AUX. HEATER. The value is read off by the hot wa-
ter sensor.
60°C(range:
50°C / 65°C)
DELAY AFTER EVU
Time in minutes. Indicates how many minutes after EVU are to pass before the auxiliary
heater may be activated.
30M(range: 0M /
120M)
EXT.AUX.HEATER
See table below for more information.
EXT.AUX.HEATER
Menu selection
Meaning
Factory setting
EXT.AUX.HEATER
Indicates whether an external auxiliary heater is installed in the system.
/ ON
INTEGRAL A3
Indicates the value of the integral when external auxiliary heater is connected.
-300(range:
-990 / INTEGRAL
A1 - 10)
TURN OFF DELAY
Indicates how long the external auxiliary heater must continue to be active after its de-
mand is no longer needed.
0M(range: 0M /
180M)
REV.V. HOT WATER
Indicates whether the exchange valve for hot water is located before or after the external
auxiliary heater. (Determines whether the external auxiliary heater may produce hot wa-
ter.)
INT / EXT
TOPH. AUX
Indicates whether the external auxiliary heater can be used for anti-legionella. The ex-
change valve must be positioned after the external auxiliary heater.
/ ON
Installation Guide
Domestic heat pumps
VMGFP202
Thermia Värmepumpar
52
Summary of Contents for Atria Optimum
Page 15: ...1 Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 15 ...
Page 72: ...Installation Guide Domestic heat pumps VMGFP202 Thermia Värmepumpar 72 ...
Page 73: ...Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 73 ...
Page 74: ...Installation Guide Domestic heat pumps VMGFP202 Thermia Värmepumpar 74 ...
Page 75: ...Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 75 ...