4.10
Testing of Controls and Safety Devices
Prior to placing the boiler in operation, the installing contractor or other responsible personnel must
perform safety and control device limit tests to ensure proper operation of the appliance. Refer to
Table 14 for recommended method(s) of carrying out these safety limit devices tests.
Table 14: Safety Device Test
Component
Test Method(s)
After Lockout
Annunciation
Actual Alarm
Message
Low Gas Pressure
Switch
Increase the setting of
the switch until the
switch trips.
Manually reset the
Concert Boiler Control
and switch. Adjust the
switch to its normal
setting.
Hard Lockout.
Gas Pressure
Switch
Low Water Cutoff
Push and hold the
LWCO test button
until the boiler control
shuts down the main
burner.
Manually reset the
Concert Boiler Control
and reset the LWCO.
Hard Lockout.
Low Water Level
Auto Reset (High
Temp) Limit
Lower the setting of
the limit so that the
boiler control shuts
down the main burner.
Adjust the limit to its
normal setting.
High Limit Auto
Reset
Water Flow Switch
Reduce the water flow
rate with a manual
shutoff valve until the
boiler shuts down.
Adjust manual valve to
normal position.
Low Water Flow
4.11
Ignition Failure
After the first ignition failure, the boiler goes into a hard lockout and a manual reset of the Concert
Boiler Control is required to restart the boiler. The boiler will then attempt to light off after it has
completed its post-purge process.
DANGER
Contact the boiler manufacturer or a qualified heating service technician if the boiler has
failed to light consecutively three times after initially resetting the Concert boiler control.