Form: 2435
Revision: 8
Arctic Installation and Operation Manual
Date: 9-19-2016
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601
Web:
www.
thermalsolutions
.com
Phone:
717-239-7642
Fax:
877-501-5212
Email:
27
Dissolved Oxygen
< 0.007 ppm
Total Iron
≤ 0.1 ppm
Total Copper
≤ 0.05
Total Hardness
≤
9
ppm
≤ 0.5
grains/gal
pH
8.3 – 10.0
Nonvolatile TOC
< 1 ppm
Oily Matter
< 1 ppm
Table 13 Recommended Feed Water
Limits
CAUTION
Thermal Solutions Standard Warranty
does not cover problems caused by
oxygen contamination of boiler water.
Thermal Solutions Standard Warranty
does not cover problems caused by scale
build-up.
When using Glycol products, all Glycol
manufacturers’ requirements, including
rust inhibitors, must be adhered. Max
50% Glycol.
WARNING
Chemicals used in treating boiler water
are toxic and/or harmful. Always use
protective clothing and equipment when
working with/near chemicals. Contact
local authorities to determine if treated
boiler water can be discharged into local
waste water system.