44
Table 21: Corrosion/Scale Inhibitors and Removal Agents
Table 22: Water Treatment Types
. Hydronic Piping
(continued)
AMP Model Max Flow
(GPM)
Min Flow
(GPM)
1000
450
35
1250
44
1500
53
2000
600
71
2500
800
88
3000
105
3500
123
4000
141
NOTICE:
This table represents the
absolute max and min flow rates allowed
and shall
not
be used to design the system
or size the circulator.
Table 23: Absolute Water Flow Rates
Table 24: Flow Rates for Glycol Systems
Producers
Fernox
Sentinel
Sotin
ADEY
Inhibitors
Protector F1/Alphi 11
X100, X500
Sotin 212
MC1+
Noise reducer
-
X200
-
-
Universal
Cleaner
Restorer
X300
-
-
Sludge remover
Protector F1, Cleaner F3
X400
Sotin 212
-
Antifreeze
Alphi 11
X500
-
-
Tightness
-
Leak Sealer F4
-
-
Treatment Type Preventive Corrective
Producer F1
X
X100
X
X
X200
X
X300
X400
X
X500
X
X
Alphi 11
X
Leaker Sealer F4
X
Sotin 212
X
MC1+
X
System Glycol
Concentration (%)
Increase Flow,
(%)
50
24
30
14
Note: Total system water volume includes
expansion tank(s) and reservoirs.
WARNING
WARNING
When using Glycol products, all Glycol
manufacturers’ requirements, including rust
inhibitors, must be adhered to. Maximum 50 %
Glycol.
Thermal Solutions' Standard Warranty does not
cover boiler failure caused by oxygen contamination
of boiler water or scale build-up.
!