41
Table 13 – Water Cooled & Remote Air Cooled Condenser Chiller Electrical Data (60 Hz) – continued
Model
Process
Pump
Size
Rated
Voltage
Allowable Power
Supply
Compressor Data
Pump
Data
Unit Data
Comp 1
Comp 2
Min
Max
RLA
1
LRA
2
RLA
1
LRA
2
FLA
3
MCA
4
MOP
5
NQW30
&
NQR30
None
230/3/60
187
253
55.8
340.0
55.8
340.0
0.0
128.1
183.9
5 HP
230/3/60
187
253
55.8
340.0
55.8
340.0
15.2
143.3
199.1
7.5 HP 230/3/60
187
253
55.8
340.0
55.8
340.0
22.0
150.1
205.9
10 HP
230/3/60
187
253
55.8
340.0
55.8
340.0
28.0
156.1
211.9
None
460/3/60
414
506
26.9
173.0
26.9
173.0
0.0
61.7
88.6
5 HP
460/3/60
414
506
26.9
173.0
26.9
173.0
7.6
69.3
96.2
7.5 HP 460/3/60
414
506
26.9
173.0
26.9
173.0
11.0
72.7
99.6
10 HP
460/3/60
414
506
26.9
173.0
26.9
173.0
14.0
75.7
102.6
None
575/3/60
518
633
23.7
132.0
23.7
132.0
0.0
54.3
78.0
5 HP
575/3/60
518
633
23.7
132.0
23.7
132.0
6.1
60.4
84.1
7.5 HP 575/3/60
518
633
23.7
132.0
23.7
132.0
8.8
63.1
86.8
10 HP
575/3/60
518
633
23.7
132.0
23.7
132.0
11.2
65.5
89.2
NQW35
&
NQR35
None
230/3/60
187
253
55.8
340.0
73.9
505.0
0.0
150.7
202.0
5 HP
230/3/60
187
253
55.8
340.0
73.9
505.0
15.2
165.9
217.2
7.5 HP 230/3/60
187
253
55.8
340.0
73.9
505.0
22.0
172.7
224.0
10 HP
230/3/60
187
253
55.8
340.0
73.9
505.0
28.0
178.7
230.0
None
460/3/60
414
506
26.9
173.0
30.4
225.0
0.0
66.1
92.1
5 HP
460/3/60
414
506
26.9
173.0
30.4
225.0
7.6
73.7
99.7
7.5 HP 460/3/60
414
506
26.9
173.0
30.4
225.0
11.0
77.1
103.1
10 HP
460/3/60
414
506
26.9
173.0
30.4
225.0
14.0
80.1
106.1
None
575/3/60
518
633
23.7
132.0
24.6
180.0
0.0
55.4
78.9
5 HP
575/3/60
518
633
23.7
132.0
24.6
180.0
6.1
61.5
85.0
7.5 HP 575/3/60
518
633
23.7
132.0
24.6
180.0
8.8
64.2
87.7
10 HP
575/3/60
518
633
23.7
132.0
24.6
180.0
11.2
66.6
90.1
NQW40
&
NQR40
None
230/3/60
187
253
73.9
505.0
73.9
505.0
0.0
168.0
242.7
5 HP
230/3/60
187
253
73.9
505.0
73.9
505.0
15.2
184.0
257.9
7.5 HP 230/3/60
187
253
73.9
505.0
73.9
505.0
22.0
190.8
264.7
10 HP
230/3/60
187
253
73.9
505.0
73.9
505.0
28.0
196.8
270.7
None
460/3/60
414
506
30.4
225.0
30.4
225.0
0.0
69.6
100.0
5 HP
460/3/60
414
506
30.4
225.0
30.4
225.0
7.6
77.2
107.6
7.5 HP 460/3/60
414
506
30.4
225.0
30.4
225.0
11.0
80.6
111.0
10 HP
460/3/60
414
506
30.4
225.0
30.4
225.0
14.0
83.6
114.0
None
575/3/60
518
633
24.6
180.0
24.6
180.0
0.0
56.3
80.9
5 HP
575/3/60
518
633
24.6
180.0
24.6
180.0
6.1
62.4
87.0
7.5 HP 575/3/60
518
633
24.6
180.0
24.6
180.0
8.8
65.1
89.7
10 HP
575/3/60
518
633
24.6
180.0
24.6
180.0
11.2
67.5
92.1
1
RLA is Rated Load Amps.
2
LRA is Locked Rotor Amps.
3
FLA is Full Load Amps.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
5
MOPD is Maximum Over-current Protection Device, complies with NEC, Section 430-53.