background image

 

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION 

 

Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in 
which you will install heater plus any adjoining rooms with door less passageways or ventilation grills 
between the rooms. 
 

1.  Determine the Volume of space in cubic feet 

 
Length X Width X Height = ___________________ cu. Ft. 
(Including adjoining rooms with door less passageways or ventilation grills between rooms) 
 
Example: 24’ (L) X 16’ (W) 8’ (H) = 3,072 cu. Ft.   
 

2.  Multiply the volume of space by 20 BTU/Hr. to determine the maximum BTU/Hr. the space can 

support. 
 
Example: 3.072 cu. Ft. X 20 BTU/Hr. = 61,440 BTU/Hr. 
   

 

 

 

 

 

 

(Maximum BTU/Hr. the room can support) 

 

3.  Add the BTU/Hr. of all the fuel burning appliances in the space 

 

Vent Free Heater _________________BTU/Hr.   
Gas Appliance #1_________________BTU/Hr. 
Gas Appliance #2_________________BTU/Hr. 
 

 

 

Example:  Vent Free Heater   

26,000 BTU/Hr. 

 

 

 

 

 

Gas Appliance #1   

35,000 BTU/Hr. 

 

 

 

 

 

 

 

 

Total 

 

61,000 BTU/Hr. 

 
The space in the prior example is a confined space because the actual BTU/hr used is more than the 
maximum BTU/hr the space can support. 
 
You must provide additional fresh air. Your options are as follows:     
Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined 
space: 

a) 

Remove door to adjoining room or add ventilation grills between rooms. See “Ventilation Air 
from Inside Building

” on next page. 

b)  Vent room directly to the outdoors. See the following 

“Ventilation Air from Outdoors” for details. 

c)  Install a lower BTU/hr heater if lower BTU/hr size makes room unconfined. If the actual BTU/hr 

used is less than the maximum BTU/hr the space can support, the space is an unconfined 
space. You will need no additional fresh air ventilation.

WARNING: 

If the area in which the heater may be operated is smaller than that defined as an 

unconfined space, or if the building is of unusually tight construction, provide adequate combustion 

and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 
54, Air for Combustion and Ventilation, or applicable local codes. 

 
 

Summary of Contents for GLDF18M-V

Page 1: ...r some of our most popular products without requiring any adjustments Our product lines consist of vent free gas wall heaters a direct vent gas wall heater line kerosene and propane forced air heaters...

Page 2: ...ater WARNING Keep the appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids WARNING Due to high temperatures the appliance should be located out of t...

Page 3: ...ings 13 The appliance must be isolated from the gas supply piping system by closing its equipment shut off valve during any pressure testing of the gas supply piping system at test pressures equal to...

Page 4: ...d that has complied with all the requirement of the authority having jurisdiction PRODUCT FEATURES SAFETY PILOT This heater has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The O...

Page 5: ...ate for heater location The Air Shutter is pre set for Liquid Propane use If using Natural Gas see Air Shutter section of manual Unit successfully tested o Installed by Company _______________________...

Page 6: ...Compare parts with package contents list and diagram above If any part is missing or damaged do not attempt to assemble install or operate the product Contact customer service for replacement parts Be...

Page 7: ...ater produces approximately one 1 ounce 30 ml of water for every 1 000 BTUs 0 3 KWs of gas input per hour Unvented room heaters are recommended as supplemental heat a room rather than a primary heat s...

Page 8: ...f the aggregate input rating of all appliances installed in that space Rooms connecting directly with the space in which the appliances are installed through openings not furnished with doors are cons...

Page 9: ...61 000 BTU Hr The space in the prior example is a confined space because the actual BTU hr used is more than the maximum BTU hr the space can support You must provide additional fresh air Your options...

Page 10: ...quired size of ventilation grills or ducts Ventilation Air from Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two permanent openings one within 12 inches of th...

Page 11: ...er creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as tobacco smoke...

Page 12: ...arance in Figure 7 are not met you must have a hood When using a hood there are still certain minimum clearances required Follow minimum clearances shown in Figure 7 when using a hood The gas log heat...

Page 13: ...anent vent opening at all times Damper manufacture shall recommend means to accomplish this such as by a screw or bolt in the edge of the damper to prevent its closing or by a hole or holes in the dam...

Page 14: ...eater So you will need to flip it over I recommend laying a cloth down so that the metal of the burner does not rub on the floor You will want to look for an oval shaped cover that has two screws You...

Page 15: ...lide any further Once done you will tighten the screw on the cylinder then seal the air shutter cover again For more information please visit our website www thermablaster com You can contact us at 87...

Page 16: ...burner holes as this can lead to sooting and an overall drop in the performance of your heater Logs should be placed sequentially from lowest to highest as the numbering indicates There are grooves on...

Page 17: ...to top of chimney and the minimum height is 10 feet Chart shows minimum opening sq in for the given height and input rate FOR MASONRY BUILT FIREPLACES Free Opening Area Of Chimney Damper For Venting C...

Page 18: ...upply This heater requires an external regulator not supplied Install the external regulator between the heater and gas supply CAUTION Avoid damage to regulator Hold gas regulator with wrench when con...

Page 19: ...1 Disconnect heater with its appliance main gas valve control valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 PSIG will damage heater regulator 2 Cap off ope...

Page 20: ...WHAT TO DO IF YOU SMELL GAS Open the window or door immediately Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supp...

Page 21: ...the Control Knob counterclockwise from the Pilot setting to the desired number setting This should be done slowly in one motion without stopping between positions Knob will only turn if you have a st...

Page 22: ...22 Figure 12 Control Panel Figure 13 Pilot System Figure 14 Pilot Blue Flame...

Page 23: ...pressed air in a can You can use a vacuum cleaner in the blow position If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dama...

Page 24: ...your gas supplier call the fire department IMPORTANT Operating heater where impurities in air exist may create odors Cleaning supplies paint paint remover cigarette smoke cements and glues new carpet...

Page 25: ...when control knob is released Both control and igniter knobs are not fully pushed down Thermocouples are not heated enough External shutoff valve of gas supply is not fully opened Thermocouple connec...

Page 26: ...leaners etc turn into white powder residue Turn heater off when using furniture polish wax carpet cleaner or similar products Heater produces unwanted odors Heater is burning vapors from paint hair sp...

Page 27: ...27 ILLUSTRATED PARTS Model GLDF18M V...

Page 28: ...nt 31 Frame assembly 10 Nozzle seat 32 LP ODS 11 LPG Nozzle 33 Chamber spacer 12 NG Nozzle 34 Battery pack 13 Air door washer 35 Bottom Strengthen strip No 2 14 Air door rod 36 Bottom Strengthen strip...

Page 29: ...ce Performed Service Date Please register your product online at www thermablaster com or send in the registration form below to our office at Reecon North America 2515 Liberty Ave Pittsburgh PA 15222...

Reviews: