Therma-Stor Ultra-Aire DEH 3000R Installer'S & Owner'S Manual Download Page 7

5.  Press the 

“CLOCK”

 button again and the day display will 

flash. Use the 

“RH”

 buttons to change the value.

6.  Don’t touch any buttons for several seconds until the display 

stops flashing, this will save your settings. If you need to 
change anything go back to step #1.

3.6 Adjusting the relative humidity “SETPOINT” 

The DEH 3000R senses the ambient relative humidity (%RH) of 
the space in which it is located, it comes factory preset to hold 
50% relative humidity.

The relative humidity 

“SETPOINT”

 (desired RH to be 

maintained) operates the dehumidifier function of the Ultra-Aire 
dehumidifier. It has no effect on the optional VENT (fresh air 
ventilation) or FAN (household air recirculation) functions if they 
are being used.

Operation

The standard range that the dehumidifier holds around your 

“SETPOINT”

 is 3%. With a setpoint of 50%, the dehumidifier 

will run until the relative humidity reaches 47%. The 
dehumidifier will then switch off until the relative humidity 
reaches 53%.

      

If the setpoint is higher than the ambient relative humidity, the 
space does not need to be dehumidified so the dehumidifier will 
not run.

Example: Setpoint: 50% RH

Current condition: 45% RH –The dehumidifier will be off (no 

“O”

 

indicator will be displayed).

If your setpoint is below the ambient condition, the dehumidifier 
will be on and 

“O”

 will display. 

Example: Setpoint: 50% RH

Current condition: 55% RH –The dehumidifier will be on (

“O” 

displayed).

3.7 Fan Setting and Operation

Use the 

“FAN”

 button to change the fan operation. There are 2 

choices for fan operation: 

“ON”

 or 

“AUTO”

. The factory preset 

is 

“AUTO”

.

“ON”

 –The fan in the Ultra-Aire dehumidifier will run 

continuously. This does not affect either the dehumidification 
or ventilation functions of the system. The system may or may 
not be ventilating or dehumidifying while the fan is running. This 
setting is commonly used for maximum air filtration and/or air 
recirculation.

“AUTO”

 – Indicates the fan will run when the DEH 3000R calls 

for dehumidification or ventilation.  If the control has not called 
for dehumidification for 3 hours, the control will automatically 
run the dehumidifier fan for 10 minutes.

After a dehumidification cycle, the fan automatically shuts off 
for 10 minutes. This pause allows the water to drain from the 
dehumidifier.

A solid 

“O”

 indicates the fan is operating. A flashing 

“O”

 

indicates the fan is in a wait mode. No 

“O”

 indicates the fan is 

OFF.

To set the operation:

1.  Press and hold the 

“FAN”

 button. The current fan setting will 

begin to flash on the display. Release the button.

2.  Press the 

“FAN” 

button to toggle between the 

“ON”

 and 

“AUTO”

 modes.

With the fan in the 

“AUTO” 

mode, the fan will operate only 

when needed by other functions of the system. The fan will 
remain OFF unless the system is dehumidifying or ventilating. 
The fan always runs during dehumidification and ventilation and 
the fan 

“O”

 icon will be lit. To completely turn the system OFF, 

use the 

“ON/OFF”

 button as described earlier.

7

DEH 3000R Dehumidifier & Ventilation System Controller

 Installation, Operation & Service Manual

Summary of Contents for Ultra-Aire DEH 3000R

Page 1: ...ASE LEAVE MANUAL FOR HOMEOWNER Dehumidifier Ventilation System Controller 2008 Therma Stor LLC Manual P N TS 506b P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales therma...

Page 2: ...95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H 2 Installation Install the DEH 3000R control panel in a central area of the structure where it...

Page 3: ...e optional motorized damper that can be installed into a fresh air duct This damper provides the ability to control fresh air ventilation using the ventilation timer function of the DEH 3000R and the...

Page 4: ...C transformer that reads 0 volts between it and the Yellow air conditioning call for cooling wire The incorrect wire will give a 20 to 28 volt reading 2 Another Yellow wire must be added to the thermo...

Page 5: ...t again to switch the fan to the ON setting c Confirm that the Ultra Aire fan is ON Ultra Aire compressor must be OFF Ventilation damper if used should be CLOSED 6 Verify optional VENT operation if el...

Page 6: ...A flashing O before the SET POINT VENT OR FAN indicates the unit is in wait mode 3 2 Setting During the set up process if you make a mistake simply continue You can always go back to adjust the settin...

Page 7: ...an Setting and Operation Use the FAN button to change the fan operation There are 2 choices for fan operation ON or AUTO The factory preset is AUTO ON The fan in the Ultra Aire dehumidifier will run c...

Page 8: ...he display Release the button 2 Press the VENT button again to switch between OPEN and CLOSED 3 Leave the control alone for 10 seconds and your settings will be saved 3 9 Damper Operation and Ventilat...

Page 9: ...schedule Repeat the steps listed above for this and the SAT SUN day and night schedules When you have finished programming your schedule either the 7 day version or the weekday weekend split version u...

Page 10: ...splice connectors provided Avoid routing parallel to high voltage wiring Maintain a distance of 2 ft or more from high voltage lines 2 Sensor connection The sensor can be mounted to a wall or ceiling...

Page 11: ...ome effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim...

Page 12: ...t to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Ther...

Reviews: