background image

5.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be removed before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type.

5.5 Blower Replacement

The centrifugal blower has a PSC motor and internal thermal 
overload protection. If defective, the complete assembly must be 
replaced.
1.  Unplug the power cord.
2.  If an outlet duct is connected to the unit, remove it.
3.  Remove the cabinet side.
4.   Remove the 4 screws holding the electrical box located next to 

the blower.

5.   Disconnect the blower leads. Black from the blower switch, 

and white from the run capacitor.

6.   Unbolt the blower capacitor from the blower motor (required 

for removal clearance). Pull the oil tubes out of the motor.

7.   Remove the nuts & bolts holding the blower outlet flange to 

the cabinet end and remove the blower.

8.   Reassembling with the new blower is the above procedure 

reversed.

5.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external overload 
run capacitor, but no start capacitor or relay (see Fig. 2).

CAUTION

ELECTRIC SHOCk HAzARD: Electrical power must be present 
to perform some tests; these tests should be performed by a 
qualified service person.

5.6A Checking Compressor Motor Circuits

Perform the following tests if the blower runs but the 
compressor does not with the blower switch OFF and the 
humidity control ON.

1.   Unplug the unit, remove the cabinet side (with two screws 

in center) and the electrical connection cover on the 
compressor top.

2.   Plug in the unit and turn the humidity control to ON. Check 

for 110 volts from compressor terminal R to overload 
terminal 3 using an AC voltmeter. If voltage is present, go 
to step 3. If no voltage, the high pressure control or relay 
are open or there is a loose connection in the compressor 
circuit. Test each component for continuity; see the 
appropriate section if a defect is suspected.

3.   Unplug the unit, then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter, 
check continuity between the points listed below.

4.   Compressor terminals C and S: No continuity indicates an 

open start winding. The compressor must be replaced. 
Normal start winding resistance 3 to 7 ohms.

5.   Compressor terminals C and R: No continuity indicates 

an open run winding. The compressor must be replaced. 
Normal run winding resistance is .5 to 2 ohms.

6.   Compressor terminal C and overload terminal 1: No 

continuity indicates a defective overload lead.

7.   Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped. Wait 10 minutes and try again. 
If there is still no continuity, it is defective and must be 
replaced.

8.   Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be 
replaced.

9.   Disconnect the yellow wires from the capacitor. Set the 

ohmmeter to the Rx1 scale. The capacitor is shorted and 
must be replaced if continuity exists across its terminals. 
If there is no needle movement with the meter set on 
the Rx100000 scale, the capacitor is open and must be 
replaced.

10.  Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 
replace the run capacitor.

11.  If the unit doesn’t start, adding a hard-start kit (relay 

& capacitor) will provide greater starting torque. If this 
doesn’t work, the compressor has an internal mechanical 
defect and must be replaced.

5.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, 
when an electrical short occurs in the compressor motor, 
the resulting high temperature arc causes a portion of the 
refrigerant oil mixture to break down into carbonaceous sludge, 
a very corrosive acid and water. These contaminants must be 
carefully removed otherwise even small residues will attack 
replacement compressor motors and cause failures.

The following procedure is effective only if the system is 
monitored after replacing the compressor to insure that the 
clean up was complete.

1.   This procedure assumes that the previously listed 

compressor motor circuit tests revealed a shorted or open 
winding. If so, cautiously smell there frigerant from the 
compressor service port for the acid odor of a burn out.

2.   Remove and properly dispose of the system charge. DO 

NOT vent the refrigerant indoors or allow it to contact your 
eyes or skin.

3.   Remove the burned out compressor. Use rubber gloves if 

there is any possibility of contacting the oil or sludge.

4.   To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps 

SANTA FE INSTALLER'S AND OWNER'S MANUAL

4

Santa Fe Installer’s & Owner’s Manual

5

Santa Fe Installer’s & Owner’s Manual

Summary of Contents for Santa-Fe

Page 1: ...ation operating and safety instructions warranty information and all ancillary products n Read and save these instructions For small usage P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www th...

Page 2: ...Size Unit Size w o duct collars 20 W x 17 D x 36 H Weight 110 lbs 2 Installation 2 1 Location The Santa Fe can be installed in a variety of locations to meet the owner s needs as listed below In all...

Page 3: ...e in 10 lengths from building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short pie...

Page 4: ...apillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates The evaporator operates in a...

Page 5: ...essor terminals C and R No continuity indicates an open run winding The compressor must be replaced Normal run winding resistance is 5 to 2 ohms 6 Compressor terminal C and overload terminal 1 No cont...

Page 6: ...ystem with the quantity and refrigerant listed on the nameplate 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plu...

Page 7: ...SANTA FE WIRING DIAGRAM 7 Santa Fe Installer s Owner s Manual Figure 2 Electrical Schematic of the Santa Fe Dehumidifier...

Page 8: ...oil 10 4021409 1 Cord Wire Harness 11 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 11 12 4021395 1 Evaporator Coil 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain 56...

Page 9: ...oving 6 screws 4 Remove the 4 screws securing the wiring box to the inside of the blower end of the dehumidifier and pull the box away from the cabinet to allow access 5 Insert a romex connector or co...

Page 10: ...are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against the bottom of the pump re...

Page 11: ...the inlet to the guides 4 Replace the filters in the unit Exhaust Collar Mounting Instructions 5 The six inch opening may be used as a fresh air inlet from outside 6 Remove the exhaust collar from the...

Page 12: ...sher and 2 screws are not used on the Santa Fe Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Santa Fe Muffler Kit Installe...

Page 13: ...anta Fe Installer s Owner s Manual Foam filter with plastic grid up Pleated filter with air flow arrow pointed down AIR FLOW Top of Dehumidifier Instructions To prevent damaging the foam filter place...

Page 14: ...and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Page 15: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680...

Reviews: