5.1 Technical Description

The Phoenix R200 50Hz uses a refrigeration system 
similar to an air conditioner’s to remove heat and moisture 
from incoming air and to add heat to the air that is 
discharged.
Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil. The refrigerant is cooled 
and condensed by giving up its heat to the air that is about 
to be discharged from the unit. The refrigerant liquid then 
passes through a filter/drier and capillary tubing which 
cause the refrigerant pressure and temperature to drop. It 
next enters the evaporator coil where it absorbs heat from 
the incoming air and evaporates.
The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the 
accumulator after leaving the evaporator coil. The 
accumulator prevents any liquid refrigerant from reaching 
the compressor. The compressor evacuates the cool 
refrigerant gas from the accumulator and compresses it to 
a high pressure and temperature to repeat the process.

5.2 Troubleshooting

No dehumidification, neither hour meter display nor 
compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 
compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 
compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Upper housing is not sealed to lower housing

No dehumidification, air mover runs but compressor does 
not.

1. Bad connection in compressor circuit
2. Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board

Air mover does not run. Compressor runs briefly but cycles 
on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty
5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board (pump phase)

Figure 5: Refrigeration system

Summary of Contents for Phoenix R200

Page 1: ...oping Handle A heavy duty retractable handle for ease of transport and reduces space for storage and stacking Recessed 30 cm Wheels For greater maneuverability on the job site and efficient storage Ro...

Page 2: ...arts and Labor 2nd 5th year 100 of sealed refrigeration system parts Dimensions Width 51cm Depth 51cm Height 85cm Weight 47kg U S Patent 7 246 503 3 Operation Place dehumidifier inside structure place...

Page 3: ...ucting to the wire duct collar by inserting the plastic duct end through the collar center and rolling the duct end outward to overlap the outside of the collar The duct and collar may then be quickly...

Page 4: ...MPORTANT DO NOT operate the unit without the filter or with a less effective filter as the heat exchanger and coils inside the unit could become clogged and require disassembly to clean 4 2 Storage an...

Page 5: ...lugged or no power to outlet 2 Defective control board 3 Loose connection in internal wiring No dehumidification neither hour meter display nor compressor run with POWER button ON 1 Defective control...

Page 6: ...rol housing grommet Figure 8 Picture of the float safety switch 6 Detach thermistor from control board jumper 7 Reassemble thermistor and dehumidifier using the above procedure in reverse 5 5 Condensa...

Page 7: ...3 YEL 7 E1 E3 E2 E5 E4 BLK 5 BRN 6 BLK 12 BLU 18 BLK 4 WHT S R C 4026354 C Figure 9 Wiring diagram 7 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 6 Options Accessories 4024750 Inta...

Page 8: ...13 Cord 1 4028256 14 Control Board 1 4028255 15 Capacitor Compressor 30 F 1 4033032 02 16 Capacitor Impeller 4 F 1 4033031 01 17 Thermistor 1 4031279 18 Handle lever 1 4026350 Description Qty Part No...

Page 9: ...he end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorize...

Reviews: