3 Maintenance

3.1 Air Filter

The Phoenix FireBird is equipped with a pleated fabric air 
filter that must be checked regularly. The standard filter 
is a MERV- high efficiency filter. Operating the FireBird 
with a dirty or obstructed filter will reduce airflow eventually 
causing the heating element to shut off.  Installing a clean 
filter or removing the obstruction to restore airflow will 
allow the heating element to operate again.
The filter can generally be vacuumed clean several times 
before needing replacement. Replacement filters can be 
ordered from the factory or purchased locally if available.

WARNING: DO NOT operate the unit without the filter or 
with a less effective filter as the heating coils inside the 
unit could become clogged and require disassembly to 
clean.

4 Service

WARNING: Servicing the Phoenix FireBird with its high 
voltage circuitry presents a health hazard which could 
result in death, serious bodily injury, and/or property 
damage. Only qualified service people should service this 
unit.
Do not operate the unit without the front panel in place. 
High voltage is present, heater burnout may result.

4.1 Technical Description

The Phoenix FireBird uses a two stage wound nichrome 
heating element to provide two heat settings depending on 
application requirements or available power.  One element 
provides low power operation and both elements together 
provide high power operation.  The heating elements and 
the blower are operated by a 24VAC control circuit and a 
number of relays and contactors.  For safety, there is an 
air pressure switch that will shut the heating elements off 
or prevent the heating elements from coming on if airflow 
is restricted at either the inlet or the outlet.  An additional 
safety switch limits the incoming air temperature to 
40°F.  This switch shuts off the heating elements and 
automatically resets when the temperature falls to 00°F.

4.2 Troubleshooting

NOTE: High Power setting requires an external 50A circuit.  
Connecting to a 30A circuit with unit set to High Power will 
result in an external circuit breaker trip.

4

www.usephoenix.com • [email protected]

Toll-Free 1-800-533-7533

Blower not running

.  Unit unplugged, no power to outlet
2.  Power switch not working or set to “THERMOSTAT” and 

no thermostat connected, or thermostat not calling for 
heat

3.  Blower Relay not operating
4.  Wiring fault inside device
5.  Defective blower or blower capacitor

Blower running but no heat

.  Airflow restricted at inlet or outlet
2.  High temperature limit reached (40°F)
3.  Heating contactor(s) not operating
4.  Wiring fault inside device
5.  Defective heating element, pressure switch, or 

temperature limit switch

5 Options and Accessories

4024750 

2” x 25’ Intake Flex Duct

4024969 

6” x 20” x 2” Pleated Media MERV-8

402475 

6” x 20” x 2” Standard Pleated Media MERV-

402264 

6” x 20” x 2” Optional Pleated Media MERV-4

4027326 

25’ Cord Kit

4027327 

Thermostat Kit 

4024440 

Kestrel 3000 Multi-Meter

Summary of Contents for Phoenix FireBird

Page 1: ...ing the 30 amp setting the FireBird produces 18 000 BTU s giving a 46 F temperature rise Internal temperature cutouts prevent the FireBird from overheating an area while the FireBird s externally loca...

Page 2: ...er Return to authorized service facility for adjustment or repair Device not intended for use directly in an area where it may fall into a bathtub or other water container DO NOT run cord under carpet...

Page 3: ...ecreases airflow which can increase outlet temperatures by up to 20 additional degrees F Install the 12 duct adapter by lining up the notch of the adapter with the rivet on the cabinet then push in th...

Page 4: ...nts together provide high power operation The heating elements and the blower are operated by a 24VAC control circuit and a number of relays and contactors For safety there is an air pressure switch t...

Page 5: ...Blue 50 AMP Receptacle Blue Black Red Black Black 3800 Watt 14 Contactor 2 L1 Blue Blower Black 230 V 24 V Optional Thermostat Master Power Switch Pressure Switch 140 Thermal Cut Out Hi Low Power Swit...

Page 6: ...ermal Switch 1 4026898 5 Pressure Switch 1 4027305 6 Blower Relay 1 4022484 7 5mf Capacitor 1 4027315 8 Heating Element 1 4027317 9 Flanged 50A Inlet 1 4027308 10 Master Power Switch 1 4027310 11 Hour...

Page 7: ...reasonable control Limitation and Exclusions If any Phoenix FireBird part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable the...

Reviews: