background image

3

www.UsePhoenix.com  •  [email protected]

Toll-Free 1-800-533-7533

2.3 Electrical Requirements

The Phoenix 270HTx plugs into a common grounded outlet 
on a 15 Amp circuit. It draws 8.9 Amps at 80°F, 60% RH. 
If used in a wet area, a ground fault interrupter (GFI) is 
required. 
If an extension cord is required, it must have a minimum of 
14 gauge conductors if 25 feet long or less and 12 gauge 
conductors if greater than 25 feet long.

2.4 Condensate Removal

The Phoenix 270HTx is equipped with an internal 
condensate pump to remove the water that is condensed 
during dehumidification. This allows the condensate to be 
pumped 30’ with the attached hose. If the condensate 
must be pumped more than 20 feet above the unit, a 
second pump must be added to relay the condensate. If 
the pump fails and the unit must be used before it can be 
replaced, the condensate can be drained by gravity (see 
Sec. 4.9).

2.5 Ducting

A detachable rectangular exhaust collar is supplied that 
will allow 10” round lay-flat duct to be attached to the 
Phoenix 270HTx outlet. 
To attach ducting to a collar, put the plastic duct end 
through the collar center and roll the duct end outward 
so that it overlaps the outside of the collar. The duct and 
collar may then be quickly attached to the Phoenix 270HTx 
by snapping the collar over the four screws at the blower 
outlet. 

2.6 Power Button

Press the POWER button to turn the dehumidifier on or off. 
When starting the dehumidifier the display will show the 
accumulated hours. Press the POWER button again to turn 
the dehumidifier off. The display will also power off.
 

2.7 Pump Purge Button

During normal operation the pump automatically cycles 
every four minutes. Press the PURGE button to remove 
condensate manually from the reservoir. There are several 

ways to manually remove water from the reservoir:
1.   Press the PURGE button once and the pump will run 

for 20 seconds

2.   Press and hold the PURGE button and the pump will 

run for up to 30 seconds

3.   Press the PURGE button while the dehumidifier is 

powered off and the pump will run for 30 seconds.

Always manually purge the water reservoir before transport 
or storage. Turn off the power and allow the plugged in 
dehumidifier to rest 15 minutes before the final purge.

2.8 Hour Meter

The digital hour meter displays the cumulative and job time 
the dehumidifier has been turned on to the tenth of an 
hour. The total and job hours measured are stored when 
the unit is unplugged. The previous total will be displayed 
the next time the unit is turned on. The job hours can be 
reset by pressing and holding the HOURS button for 5 
seconds when the unit is operating.

2.9 HOURS Button

Press the HOURS button when the dehumidifier cannot 
be plugged in and the hour meter needs to be read. 
The digital hour meter will briefly display the last saved 
cumulative time for 10 seconds.

2.10 DEFROST Light

The DEFROST light turns on when the unit is in defrost 
mode indicating when the compressor is off.

DRYING TIP: Air’s ability to absorb moisture from wet 
surroundings and the Phoenix 270HTx’s ability to remove 
moisture from that air is greatly improved at higher 
temperatures. We recommend that the area to be dried be 
heated to over 70°F if possible. Less drying time will be 
required and efficiency will improve.

2.11 Low Pressure Protection

If the low side refrigerant drops into a low pressure situa-
tion that may harm the compressor, the solid state con-
trols will sense the refrigerant conditions and shut off the 
compressor until the system automatically resets itself. 

 The solid state control monitors and compares the ambi-
ent temperature and refrigerant conditions to ensure the 
system is protecting compressor at all times.   The control 
protects the compressor from damage by monitoring 
cycles, pressures, and system performance.

2.12 Defrost Cycle

If the low side refrigerant temperature drops below the 
defrost set point, due to excessive frost formation on 
the evaporator coil, the thermistor activates the solid 
state control and the defrost light.  The control cycles 
the compressor “off” and “on” by monitoring thermistor 
temperature.  The air mover will continue to run, causing 
air to flow through the evaporator coil. The air will melt the 
ice that formed on the evaprator.  

When the air temperature and/or humidity increases, the 
evaporator temperature will rise and the thermistor will end 
the defrost cycle restarting the compressor.  

Summary of Contents for Phoenix 270HTx

Page 1: ...12 intake 10 exhaust Solid State Controls Easy to read and operate Recessed 12 Wheels Allows greater maneuverability on the job site and efficient storage Rolls over obstacles with ease MERV 11 Pleat...

Page 2: ...walls and other obstructions to air flow Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 270HTx 2 2 2 Location 2 2 3 Electrical Requirements 3 2 4 Conden...

Page 3: ...oir before transport or storage Turn off the power and allow the plugged in dehumidifier to rest 15 minutes before the final purge 2 8 Hour Meter The digital hour meter displays the cumulative and job...

Page 4: ...d If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyet...

Page 5: ...cuit 2 Obstruction prevents impeller rotation 3 Defective air mover 4 Defective control board Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humid...

Page 6: ...ng the pump bracket to the base 5 Replace the pump hose wiring bolts and cover in the reverse order 4 6 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge mus...

Page 7: ...7 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram 4028595...

Page 8: ...peller 15mfd 371V 1 4025224 14 Thermistor Coil 1 4027278 15 Thermistor Bulkhead 1 4028581 16 Battery AA 4 8523901 17 Cord 115V 25 1 4025078 18 Compressor 10 2KBTU R410a 1 4029176 19 Overload Compresso...

Page 9: ...9 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 10: ...anty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Reviews: