4.2 Troubleshooting

No dehumidification, neither hour meter display nor 

compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 

compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 

compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Low refrigerant charge
7.  Defrost thermistor detached from coil
8.   Loose connection to low pressure switch.

No dehumidification, air mover runs but compressor does 

not.

1.   Bad connection in compressor circuit
2.   Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board
7.  Low refrigerant charge
8.   Loose connection to low pressure switch.

Air mover does not run. Compressor runs briefly but cycles 

on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover
4.  Defective control board.

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty

5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose front cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting
10. Defrost thermistor detached from coil

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board

Unit pumps water automatically but not when PURGE button 

is pushed.

1. Bad connection in PURGE button circuit
2. Defective control board

Evaporator coil frosted continuously, low dehumidifying 

capacity.

1. Defrost thermistor loose or defective
2. Low refrigerant charge

Compressor runs with POWER button OFF.

1. Defective control board
2. Upper housing not sealed to tower

4.3 Air Mover Replacement

The blower has a PSC motor and internal thermal overload 

protection. If defective, the complete assembly must be 

replaced.
1.   Unplug power cord
2.   Remove the front cover
3.   Remove the 5 screws attaching blower inlet ring
4.  Remove the 4 screws mounting impeller to underside of 

base plate

5.   Disconnect the blower leads
6.   Reassemble the new blower using the above procedure 

in reverse

4.4 Thermistor Replacement

The defrost thermistor is attached to the refrigerant suction 

line between the accumulator and the evaporator.
To replace thermistor:
1.   Unplug the dehumidifier
2.   Remove the front cover

Summary of Contents for Phoenix 200 HT

Page 1: ...Faster drying and superior static pressure for ducting Multiple Ducting Options 12 intake 10 exhaust Solid State Controls Easy to read and operate Recessed 12 Wheels Allows greater maneuverability on...

Page 2: ...t from walls and other obstructions to air flow Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 200HT 2 2 2 Location 2 2 3 Electrical Requirements 3 2 4...

Page 3: ...e plugged in dehu midifier to rest 15 minutes before the final purge 2 8 Hour Meter The digital hour meter displays the amount of time the dehumidifier has been turned on to the tenth of an hour The h...

Page 4: ...an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyethylene To flush 1 Run the hose to a drain 2 Plug in the un...

Page 5: ...but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defecti...

Page 6: ...ately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type 4 7...

Page 7: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram LL Therma Stor...

Page 8: ...e 1 4023080 11 Control Board 1 4030083 12 Capacitor Compressor 45mfd 370V 1 4033032 05 13 Capacitor Impeller 15mfd 370V 1 4033031 07 14 Thermistor 1 4031279 15 Cord 1 4032297 16 TOS 8 2 KBTU R410A 1 4...

Page 9: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 10: ...anty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Reviews: