background image

4

www.UsePhoenix.com  •  [email protected]

Toll-Free 1-800-533-7533

temperature inside the condenser rises.  By removing the 

bypass magnet from the bypass openings, additional airflow 

is directed over the condenser and less airflow is directed 

across the evaporator.  The airflow differences improve the 

dehumidifier efficiency.
Below 90F – When the Phoenix 200 HT is used in low 

temperature conditions (below 90F), the refrigerant 

temperature inside the condenser lowers.  By adding a 

bypass magnet to the bypass openings, additional airflow 

is added through the evaporator. The airflow difference 

improves the dehumidifier efficiency.

3 Maintenance

3.1 Air Filter

The Phoenix 200HT is equipped with a pleated fabric air filter 

that must be checked regularly. The standard filter is a MERV-

11 high efficiency filter. Operating the unit with a dirty filter 

will reduce the dehumidifier’s capacity and efficiency and 

may cause the compressor to cycle off and on unnecessarily 

on the defrost control.

IMPORTANT:

  DO NOT operate the unit without the filter 

or with a less effective filter as the heat exchanger and 

coils inside the unit could become clogged and require 

disassembly to clean.

3.2 Storage

There are two issues to consider when the Phoenix 200HT 

is stored between uses. Both pertain to the water trapped 

in the unit: damage caused by freezing or biological growth. 

The effect of the trapped water can be greatly reduced if 

precautions are taken to remove as much as possible before 

storage.
1.  Use the pump purge switch (see Sec. 2.7)  to reduce the 

water level in the reservoir.

2.  Stretch the hose flat to drain it completely. Raise one 

end above your head and spool to drain water out of the 

other end.

If the unit will not be exposed to freezing temperatures, an 

alternative to reduce biological growth is to flush the unit 

with a bio-fungicide that is approved for use with copper, 

aluminum and polyethylene. To flush:
1.  Run the hose to a drain.
2.  Plug in the unit but do not turn it on.
3.  Remove the air filter. Slowly pour a quart of the chemical 

through the heat exchanger

4.  Hold in the pump purge switch to reduce the water level 

in the reservoir.

5.  Flush with water.

4 Service

CAUTION: Servicing the Phoenix 200HT with its high 
pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, 
serious bodily injury, and/or property damage. Only 
qualified service people should service this unit.

4.1 Technical Description

The Phoenix 200HT uses a refrigeration system similar to an 

air conditioner’s to remove heat and moisture from incoming 

air, and to add heat to the air that is discharged (see Fig. 2).

Hot, high pressure refrigerant gas is routed from the 

compressor to the condenser coil (see Figure 2). The 

refrigerant is cooled and condensed by giving up its heat 

to the air that is about to be discharged from the unit. The 

refrigerant liquid then passes through a filter/drier and 

capillary tubing which cause the refrigerant pressure and 

temperature to drop. It next enters the evaporator coil where 

it absorbs heat from the incoming air and evaporates.
The evaporator operates in a flooded condition, which means 

that all the evaporator tubes contain liquid refrigerant during 

normal operation. A flooded evaporator should maintain 

constant pressure and temperature across the entire coil, 

from inlet to outlet.

The mixture of gas and liquid refrigerant enter the 

accumulator after leaving the evaporator coil. The 

accumulator prevents any liquid refrigerant from reaching the 

compressor. The compressor evacuates the cool refrigerant 

gas from the accumulator and compresses it to a high 

pressure and temperature to repeat the process.

Figure 2: Refrigeration system

Summary of Contents for Phoenix 200 HT

Page 1: ...Faster drying and superior static pressure for ducting Multiple Ducting Options 12 intake 10 exhaust Solid State Controls Easy to read and operate Recessed 12 Wheels Allows greater maneuverability on...

Page 2: ...t from walls and other obstructions to air flow Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 200HT 2 2 2 Location 2 2 3 Electrical Requirements 3 2 4...

Page 3: ...e plugged in dehu midifier to rest 15 minutes before the final purge 2 8 Hour Meter The digital hour meter displays the amount of time the dehumidifier has been turned on to the tenth of an hour The h...

Page 4: ...an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyethylene To flush 1 Run the hose to a drain 2 Plug in the un...

Page 5: ...but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defecti...

Page 6: ...ately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type 4 7...

Page 7: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram LL Therma Stor...

Page 8: ...e 1 4023080 11 Control Board 1 4030083 12 Capacitor Compressor 45mfd 370V 1 4033032 05 13 Capacitor Impeller 15mfd 370V 1 4033031 07 14 Thermistor 1 4031279 15 Cord 1 4032297 16 TOS 8 2 KBTU R410A 1 4...

Page 9: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 10: ...anty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Reviews: