background image

quest

Asset Protection and IAQ Solutions

quest

1-800-533-7533 

HI-E DRY 195 

Installation, Operation and Maintenance Instructions

  

12

www.QuestProtect.com

[email protected]

quest

quest

10. Reconnect the wires to the compressor and capacitor; plug in and turn on the unit. If the compressor 

fails to start, replace the run capacitor.

11. If the unit still does not start, adding a hard-start kit will provide greater starting torque. If this does not 

work, the compressor has an internal mechanical defect and must be replaced.

5.6B Replacing a Burned Out Compressor
The refrigerant and oil mixture in a compressor is chemically very stable under normal operating conditions. 
However, when an electrical short occurs in the compressor motor, the resulting high temperature arc causes 
a portion of the refrigerant oil mixture to break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise even small residues will attack replacement 
compressor motors and cause failures.

The following procedure is effective only if the system is monitored after replacing the compressor to insure 
that the clean up was complete.

1.  This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or 

open winding. If so, cautiously smell the refrigerant from the compressor service port for the acid odor of 
a burn out. 

  WARNING: The gas could be toxic and highly acidic. If no acid odor is present, skip down to the 

section on changing a non-burn out compressor.

2.  Remove and properly dispose of the system charge. DO NOT vent the refrigerant or allow it to contact 

your eyes or skin.

3.  Remove the burned out compressor. Use rubber gloves if there is any possibility of coming in contact 

with the oil or sludge.

4.  To facilitate subsequent steps, determine the type of burn out that occurred. If the discharge line shows 

no evidence of sludge and the suction line is also clean or perhaps has some light carbon deposits, the 
burn out occurred while the compressor was not rotating. Contaminants are therefore largely confined to 
the compressor housing. A single installation of liquid and suction line filter/driers will probably clean up 
the system.

  If sludge is evident in the discharge line, it will likely be found in the suction line; this indicates the 

compressor burned out will running. Sludge and acid have been pumped throughout the system. Several 
changes of the liquid and suction filter/driers will probably be necessary to cleanse the system.

5.  Correct the system fault that caused the burn out. Consult the factory for advice.
6.  Install the replacement compressor with a new capacitor and an oversized liquid line filter.
  In a running burn out, install an oversized suction line filter/drier between the accumulator and 

compressor. Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to 
prevent the oil hole from becoming plugged. A standing burn out does not require a suction line filter/
drier.

7.  Evacuate the system with a good vacuum pump and accurate vacuum gauge. Leave the pump on the 

system for at least an hour.

8.  Operate the system for a short period of time, monitoring the suction pressure to determine that the 

suction filter is not becoming plugged. Replace the suction filter/drier if pressure drop occurs. If a severe 
running burn out has occurred, several filter/driers may have to be replaced to remove all of the acid and 
moisture.

Summary of Contents for HI-E Dry 195

Page 1: ...s QuestProtect com Read and Save These Instructions Specifications subject to change without notice TS 622 04 14 1 HI E DRY 195 HI E Dry 195 Controlled by a dehumidistat with settings from 20 to 80 pe...

Page 2: ...sh Air 6 2 5 Optional Remote Humidity Control 7 2 6 Hard Wiring The HI E Dry 195 7 3 Operation 7 3 1 Humidity Control Adjustment 7 3 2 Fan Switch 7 3 3 Defrost Control Adjustment 8 3 4 Low Pressure Co...

Page 3: ...and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your HI E Dry 195 dehumidifier READ AND SAVE THESE INSTRUCTIONS It is designed to be installed I...

Page 4: ...ht 180 Lb 214 Lb Minimum Performance at Set Conditions Intake Air 70 60 80 60 Water removal day 156 Lbs 200 Lbs Pints KWH 5 4 5 9 2 Installation 2 1 Location The HI E Dry 195 can be installed in a var...

Page 5: ...rooms e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control There are several potential disadvantages to using this method First humid air is...

Page 6: ...diameter or equivalent Grills or diffusers on the duct ends must not excessively restrict airflow Isolated Areas Effective dehumidification may require that ducting be branched to isolated stagnant a...

Page 7: ...ord and the strain relief bushing 3 Trim and strip the wire ends for wire nuts 4 Use a 1 2 connector to attach the hard wiring to the HI E Dry 195 Use a minimum of 3 14 wire Comply with all state and...

Page 8: ...e unit warms up it may cycle several times 4 Maintenance 4 1 Air Filter The HI E Dry 195 is equipped with two 2 thick MERV 8 pleated fabric air filters that must be checked regularly Operating the uni...

Page 9: ...iquid refrigerant from reaching the compressor The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process 5 3 Tro...

Page 10: ...irty Sec 4 1 5 Defective defrost thermostat Sec 5 10 6 Low refrigerant charge Sec 5 4 7 Air leak such as loose cover 8 Defective compressor Sec 5 6 9 Restrictive ducting Sec 2 4 Pump does not pump wat...

Page 11: ...120 volts between a the relay terminal that the black wire from the compressor connects to and b the capacitor terminal with the 2 white wires 1 red wire 1 brown wire connected If voltage is present...

Page 12: ...to contact your eyes or skin 3 Remove the burned out compressor Use rubber gloves if there is any possibility of coming in contact with the oil or sludge 4 To facilitate subsequent steps determine the...

Page 13: ...ermostat is attached to the refrigerant suction tube between the accumulator and compressor If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil the th...

Page 14: ...TOR BRN WHT COMPRESSOR COMPRESSOR COMPRESSOR OVERLOAD PART NO REV 4023609 C RUN CAPACITOR RUN CAPACITOR YEL BRN TIMER TIMER SWITCH WHT WHT WHT PNK MOTOR WHT BLK BLK BLK BLK GRN 115VAC 60HZ 1PH CONDENS...

Page 15: ...25741 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip 12 4021823 1 Defrost Timer 4021823 13 4023603 1 Duct Collar Kit Optional 14 4021799 2 Filter Air 2 X 16 X 16 Grainger P N 6B958 15...

Page 16: ...Installation Operation and Maintenance Instructions 16 www QuestProtect com sales QuestProtect com quest quest 8 ACCESSORIES HI E Dry 195 Dehumidifier PART NO DESCRIPTION 4023684 Duct Collar Kit 40201...

Page 17: ...anty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care cor...

Reviews: