1-877-420-1330
Quest 185 Cool
Installation, Operation and Maintenance Instructions
4
www.QuestHydro.com
1. Intended Application for Quest 185 Cool Dehumidifier
In order to efficiently control humidity levels, the area in which the dehumidifier is to be operated must be free of water
intrusion or excessive fresh (outside) air infiltration. Before installing the Quest 185 Cool Dehumidifier, water intrusion
and air infiltration problems should be addressed or noted in calculations.
2. Registrations
The Quest 185 Cool conforms to unified standard UL 474 and CSA Standard C22.2 No. 92.
3. Parts List Included
• Quest 185 Cool Dehumidifier
• Quest 185 Cool Condensing Unit
• Quest 185 Cool Installation Instructions
• Quest 185 Cool Leveling Feet
4. Specifications @ 80°F/60% RH
Dehumidifier:
4037391
Power (Watts):
160
Supply voltage:
110-120 VAC -
1 Phase - 60 Hz.
Current Draw (Amps):
1.4
Energy Factor
(L/kWh):
3.1
Operating Temp:
56°F Min - 95°F Max
Water Removal (Pints/Day):
Efficiency (Pints/kWh):
184
6.6
Air Filter (MERV-11):
Size: 16" x 20" x 2"
Power Cord
14ga 10’, NEMA 5-15P
Drain Connection:
3/4” Threaded NPT
Refrigerant Type:
R410A
Dimensions:
Width:
Height:
Length:
Weight:
20.25"
21.75"
38"
109 lbs
Condenser:
4037392
Power (Watts):
1080
Supply voltage:
110-120 VAC -
1 Phase - 60 Hz.
Current Draw (Amps):
9.7
Minimum Circuit
Ampacity:
20
Maximum Fuse/Breaker
20
Operating Temp:
40°F Min - 115°F Max
Power Cord
Hard-Wired
Refrigerant Type:
Refrigerant Amount:
R410A
2lb. 4oz.
Dimensions:
Width:
Height:
Length:
Weight:
10"
25.5"
33"
75 lbs