7.2 Troubleshooting

No dehumidification, neither blower nor compressor 
run with fan switch OFF. 

1. Unit unplugged or no power to outlet.
2. Humidity control set too high or defective.
3. Loose connection in internal wiring.

No dehumidification, compressor does not run but 
blower runs with fan switch OFF and humidity control 
turned to ON.

1. Defective compressor or compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defrost thermostat open.

Blower runs with fan switch OFF, but compressor 
cycles on & off.

1.  Low ambient temperature and/or humidity causing unit 

to cycle through defrost mode.

2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.

Blower does not run with fan switch in either position. 
Compressor runs briefly but cycles on & off.

1. Loose connection in blower circuit.
2. Obstruction prevents impeller rotation.
3. Defective blower.
4. Defective blower switch.

Evaporator coil frosted continuously, low 
dehumidifying capacity.

1. Defrost thermostat loose or defective.
2. Low refrigerant charge
3. Dirty air filter or air flow restricted.

7.3 Defrost Thermostat

The defrost thermostat is attached to the refrigerant suction tube 
between the accumulator and compressor. It will automatically 
shut the compressor off if the low side refrigerant temperature 
drops due to excessive frost formation on the evaporator coil. 
The blower will continue to run, causing air to flow through the 
evaporator coil and melt the ice. When the ice has melted, the 
evaporator temperature will rise and the thermostat will restart the 
compressor.

8. Service Parts List

PART NO. 

DESCRIPTION

4021395  

Coil, Evaporator

4021396 

Coil, Condenser

4021470 

Thermostat, Defrost Control

4021589 

Tube, CU, CPLRY

4025087 

Filter, Drier

4021469 

Controller, Humidity, Face Mount

4026827 

Compressor

4025076 

Fan, Motorized Impeller

4025224 

Capacitor, Impeller

4027108 

Capacitor, Run

4026828 

Overload, Compressor

4025560 

Switch, Rocker, On-Offr

9. Accessory/Replacement Parts

PART NO. 

DESCRIPTION

4021475 

Filter, Air

4021626 

Hose, Vinyl

4025264 

Trap, Drain

4021495 

Knob, Plastic, Black

4025249 

Outlet Collar

To order, contact your reseller  

or call 1-800-533-7533.

SANTA FE HC OWNER’S AND INSTALLER’S MANUAL

6

Santa Fe HC Installer’s & Owner’s Manual

Duct Collar Kit

Optional 10" Inlet Collar

Included 10" Outlet Collar

Summary of Contents for 4025081

Page 1: ...1 08 For small usage P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com Free standing Moisture Control for Large Areas INSTALLER S OWNER S MANUAL HVAC INST...

Page 2: ...80 F 60 RH Operating Temp 56 F min 100 F max Air Flow 323 CFM without external ducting 307 CFM 20 WG external static 285 CFM 40 WG external static Refrigerant Charge 1 lb 12 oz R22 Duct Connections Ro...

Page 3: ...air flow path between the two rooms e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control WARNING Before installing the dehumidifier in the...

Page 4: ...Route the drain hose through the trap as shown below in Figure 6 Position the trap on the hose approximately 12 away from the unit 4 Ducting 4 1 Optional Ducting Kit 10 collars may be attached to acc...

Page 5: ...to the options and accessories table in this document 6 2 Blower Oiling The blower motor has been lubricated at the factory for many years of normal operation 7 Service WARNING Servicing the Santa Fe...

Page 6: ...charge 3 Dirty air filter or air flow restricted 7 3 Defrost Thermostat The defrost thermostat is attached to the refrigerant suction tube between the accumulator and compressor It will automatically...

Page 7: ...SANTA FE HC OWNER S AND INSTALLER S MANUAL 7 Santa Fe HC Installer s Owner s Manual 10 Wiring Diagram...

Page 8: ...de panel of the dehumidifier by removing 9 hex screws Remove four screws on back of unit to expose electbox 4 Remove the 4 screws securing the wiring box to the inside of the blower end of the dehumid...

Page 9: ...shown STEP 2 Pre drilled mounting holes are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealin...

Page 10: ...applies to residential applications and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper re...

Page 11: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680...

Reviews: