 6. Technical data

• Operating voltage:

 

22 V AC +10 % –15 %

• Frequency:  

50 Hz

• Power consumption:   < 5.5 W
• Standby min.:  

< 3 W

• Permissible ambient 
  temperature:  

–20 °C ... +55 °C

• Protection class:  

II when properly installed

• Protection rating:  

IP 44 in accordance with EN 60529

• Cable power
  supply: 

max. cable cross-section 1.5 mm

2

• COM port: 

EIB/KNX bus line: TYPE YCYM or  

   

Y(ST)Y; telecommunication line  

   

J-Y(ST)Y, length to 100 m

• Mast installation:  

Dm 50–60 mm (accessory 9070380)

• Measurement range
 – Wind sensor: 

1–20 m/s

 – Temperature sensor:  –30 °C to +60 °C
 – Brightness sensor (3): 1–130000 lux
• Rain sensor: 

Rain/no rain

• Mode of operation: 

Type 1

• Pollution degree: 

4 (2 inside the housing, since IP 44)

• Rated impulse voltage:  0.33 kV

Please refer to the Handbook for LUXOR 411 for detailed  
functional descriptions.

2

Theben AG

Hohenbergstr. 32
72401 Haigerloch
GERMANY
Phone  +49 7474 692-0  
Fax +49 7474 692-150

SERVICE

Phone  +49 7474 692-369  
Fax +49 7474 692-207
[email protected]

Addresses, telephone numbers etc. at
www.theben.de

5. Electrical connection

Plug-in terminals for connecting 
the operating voltage
and the COM port

Washer

Rubber seal

Feed in lines 

  Feed the cables through the rubber seals, strip cores to 8 mm  

  and insert in the terminals (provide flexible cores with  
  crimp terminals).

Remove cables

  Remove cables by rotating and pulling out of the  

 terminals. 

Mast or corner bracket fixing

The weather station can also be attached to a mast with mast or 
corner fixing (accessory 9070380).  

This installation method is recommended if wind is to be registe-
red from all directions.

The operating voltage is extra-low voltage SELV. 
The COM port is function low voltage FELV.

LUXOR 440

LUXOR 411

22 V AC

COM

Connecting further 
LUXOR devices

LUXOR 440