background image

LAN top2 software

The LAN top2 software is available for download to  

www.theben.de/produkt/6490900

. In addition to functional 

description, technical details, the software is available under  

 Downloads.

 Starting LAN top2 software. 

  The home page opens with the following window:

  1. How can you find LAN modules?

  – automatically in the LAN: The LAN top2 software searches 
     for the connected LAN modules and lists them.
  – by entering an IP by hand: The IP address of a LAN module  
     can be entered directly in a separate window.
  – by reading IPs from a file: A file in text format is selected 
     that lists the IP addresses. 

  2. Response at restart

  – show this window again
  – execute last choice

 Make selection.

2

A list of IP addresses then appears (see fig.).

 Select IP address. 

You can change the IP addresses and the name of the EM LAN 
top2 module.

 Press

 Change IP address/name

 enter new IP address/

  new name and press 

OK

.

 Press 

Connect

.

• Cable types for DATA bus (max.100 m): Sheathed cable:  
   

NYM (3 x 1.5 mm

2

); MSR cable: 

   

PYCYM, YCY (2 x 2 x 0.8 mm

2

   

telephone cable: J-Y(St)Y (2 x 2 x 0.8 mm

2

)

   

Bell wire: YR

• Power supply at DATA bus: 50 mA 
   

(maximum current at DATA bus: 

   

500 mA)

• Mode of operation:  Type 2 in accordance with EN 60730-1
• Pollution degree:   2

Technical data

• Operating voltage:  230 V~, +10 %/-15 %
• Frequency:  

50-60 Hz

• Power consumption: typically 7.5 VA
• DATA bus: 

Bus voltage: 15 V DC, low

   

voltage in protection class III (SELV)

• Permissible ambient temperature: –30 °C ... +50 °C
• Protection class: 

II in accordance with EN 60730-1 with 

   

designated installation

• Protection rating:  IP 20 in accordance with EN 60529

Summary of Contents for EM LAN top2

Page 1: ...us Up to 4 timers can be connected to 1 EM LAN top2 LAN module via DATA bus DATA bus cable length max 100 m Setting up the EM LAN top2 LAN module The EM LAN top2 LAN module is supplied without a fixed IP address and is configured as a DHCP client 1 In network with DHCP server Use LAN top2 software to let the EM LAN top2 module search and select 2 Without DHCP server Use a LAN cable to connect the ...

Page 2: ...lection 2 A list of IP addresses then appears see fig Select IP address You can change the IP addresses and the name of the EM LAN top2 module Press Change IP address name enter new IP address new name and press OK Press Connect Cable types for DATA bus max 100 m Sheathed cable NYM 3 x 1 5 mm2 MSR cable PYCYM YCY 2 x 2 x 0 8 mm2 telephone cable J Y St Y 2 x 2 x 0 8 mm2 Bell wire YR Power supply at...

Page 3: ...cial programmes and reset the operating hours counter You can also change the date time and enter or delete PIN see fig Select action and press Send The connected time switches appear e g TR 644 top2 RC see fig Select desired time switch You can also change the name of the time switch here The new name is only stored in the LAN software on the PC and not and not in the EM LAN top2 module Press Cha...

Page 4: ... file ot2 You can input display and change the received ot2 file using the OBELISK top2 software 4 Service address Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Telephone 49 0 74 74 6 92 0 Fax 49 0 74 74 6 92 150 Hotline Telephone 49 0 74 74 6 92 369 Fax 49 0 74 74 6 92 207 hotline theben de Addresses telephone numbers etc www theben de You can send and receive ot2 files for the OBELISK top2 ...

Reviews: