Detection Range

 (Mounting Height = 3.0m)

 Seated persons

Walking persons

HVAC

*) The presence output can be tapped on any master.

*)

“Master-Master” Parallel Connection 
(Multiple Lighting Rows)

A parallel connection of several masters is also possible 

where each master uses its own brightness measure-

ment to control a lighting row. Delay times and bright-

ness threshold are set on each master individually. The 

switched load is split up between the individual masters, 

and the presence continues to be detected by all detec-

tors together. The presence output can be tapped on any 

master.

Location

Detection Range

The square detection ranges ensure a safe and simple 

planning. Connected in parallel, they allow the entire 

room to be covered. Please note that the detection range 

for seated persons and walking persons differ in their 

extension.
The recommended mounting height is 2,0m - 3,0m. 

The sensitivity of the detector decreases with increasing 

mounting height. From a mounting height of 3m walking 

movements are required for detection, and the detection 

ranges of multiple detectors should overlap in their fringe 

zones.

Brightness Measurement

The compact office presence detector is equipped with a 

mixed light measurement. As the mixed light measure-

ment is influenced by artificial light, the brightness for 

indirect lighting on the site of installation must not 

exceed 2000Lux (for brightness threshold > 200Lux).
If the brightness threshold value is set to “On”, the 

brightness measurement is deactivated (no influence by 

brightness desired). 

Suitable Lamps

The compact office presence detector is designed for use 

with fluorescent lights (FL/PL) as well as halogen/incan-

descent lights. 
The maximum number of electronic ballast that can be 

controlled is limited due to the high inrush currents. In 

case of high loads, this can be overcome by using an 

external protection.
In parallel connection, the load can be split up between 

multiple detectors. All loads switched must be provided 

with adequate interference suppression.

The detection range in side view (top) and top view 

(bottom).

Seated Persons:

The values given refer to the restricted detection range 

for movements taking place at table height, i.e. approx. 

0.80m above the floor. From a mounting height of > 

3m, the sensitivity of the detector is limited, and more 

distinct movements are required for detection.

Walking Persons

For walking persons, the entire detection range is valid 

with a small tolerance in the fringe zone (+/- 0.5m).

Lighting row 1

Push button 1

 

/ switch 1

Push button 2

 

/ switch 2

Lighting row 2

Master-Master Schematic Wiring Diagram for 

Two Lighting Rows

M‘height 

Seated persons  

Walking persons

2,0m 

3,0m x 3,0m 

4,5m x 4,5m ± 0,5m

2,5m 

4,0m x 4,0m 

6,0m x 6,0m ± 0,5m

3,0m 

4,5m x 4,5m 

7,0m x 7,0m ± 1,0m

3,5m 

       - - 

8,0m x 8,0m ± 1,0m

compact

power

L

N P

S A

B1 B2

compact

power

L

N P

S A

B1 B2

L
N

Master 1

Master 2

Summary of Contents for compact office

Page 1: ...f learning characteristic i e the unit is able to automatically extend the switch off delay time to max 15min or reduce it to the minimum set time The switch off delay time will not be changed if it is set to 2 min or less Fully or Semi automatic Operation The compact office optionally allows fully automatic lighting control for more convenience or semi automatic control for better energy saving r...

Page 2: ...are present all the time If the con tact is closed the switch off delay time 10s 120min is restarted at each detection of movement Room Surveillance If the switch on delay is set to Surveillance the sensi tivity of the switched output for presence is reduced The contact closes in case of distinct move ments only and thus reliably indicates the presence of persons The switch off delay time remains ...

Page 3: ...rightness for indirect lighting on the site of installation must not exceed 2000Lux for brightness threshold 200Lux If the brightness threshold value is set to On the brightness measurement is deactivated no influence by brightness desired Suitable Lamps The compact office presence detector is designed for use with fluorescent lights FL PL as well as halogen incan descent lights The maximum number...

Page 4: ...vation of pulse function Switch off delay for presence HVAC surveillance Switch on delay for HVAC activation of room surveillance function DIP switches DIP1 Lighting control fully semi automatic DIP2 Push button function Room Corridor DIP3 Push button switch control DIP6 Operation mode normal operation test Mechanical safety lock The mechanical lock serves to secure the sensor module firmly on the...

Reviews: