Theben compact office Quick Start Manual Download Page 2

Theben AG

Subject to change without notice. Errors and omissions excepted.

HVAC

Lighting row 1

push 

button
1
2

HVAC

*) 

Lighting row 

HVAC / surveillance

HVAC/surveillance

Lighting row 2

Switching Behavior in Semi-automatic Mode

The behavior in semi-automatic operation is basically the 

same as in fully automatic operation, except for the fact 

that the lighting is never switched on automati-cally, i.e. 

it must always be switched on manually.

“Room or Corridor” Push Button Function 

By means of the DIP switches, the function of the push 

button(s) can be set to “Room” or “Corridor”. In the 

“Room” position, the lighting can always be switched on 

and off manually, whereas in the “Corridor” position, the 

detector is used as staircase lighting timer, i.e. the light 

cannot be switched off manually. 

Pulse Function

In order to control existing staircase lighting timers, the 

switch off delay time can be set to “Pulse”. In this posi-

tion, the switched output for light generates a short pulse 

(duration 0.5s) every 10 seconds in case of presence and 

darkness.

Switched Output for Presence

The switched output for presence is used for HVAC cont-

rol and room surveillance. The switching behavior of the 

potential-free contact is only affected by presence and not 

by brightness. The contact closes in case of presence and 

opens in case of absence. The contact is not affected by 

the push buttons.

HVAC Control with Switch-on Time Delay

The switch on delay (0s - 10min) prevents that the system 

is switched on immediately. The contact does not close 

before the switch on delay time has elapsed, provided of 

course that persons are present all the time. If the con-

tact is closed the switch off delay time (10s - 120min) is 

restarted at each detection of movement. 

Room Surveillance

If the switch on delay is set to “Surveillance”, the sensi-

tivity of the switched output for presence is reduced. The 

contact closes in case of distinct move-ments only and 

thus reliably indicates the presence of persons. The switch 

off delay time remains active. The switch-on time delay is 

inactive. 

Interconnection

In single unit operation, the compact office is set up to 

detect presence and brightness and controls the lighting 

and HVAC/surveillance by means of its two contacts. If 

the detection range of one detector is insufficient (e.g. 

in case of very large rooms) up to 10 detectors can be 

connected in parallel by interconnecting the P-terminals 

of the detectors. Depending on the application, a detec-

tor is referred to as master or slave. Master and slave are 

identical devices with different wiring. 

“Master-Slave” Parallel Connection

The detector controlling the lighting is always referred to 

as master. The brightness measurement and the adjust-

ment of all potentiometers is done centrally on the mas-

ter. Any push buttons are connected to the master only, 

and the entire load is switched by the master. Any further 

detectors are referred to as slaves. Their only task is to 

supply the presence information.

Schematic Wiring Diagram - Single Unit Operation

Master-Slave Parallel Circuit Operation for 

One Lighting Row

Lighting

Push button/

switch

Push  
button

Lighting

Push button

 

/switch

Master-Master Parallel Circuit Operation 
for Two Lighting Rows

Schematic Wiring Diagram for Master-Slave Parallel 

Circuit Operation

compact

power

L

N P

S A

B1 B2

compact

power

L

N P

S A

B1 B2

L
N

Master

Slave

compact

power

L

N P

S A

B1 B2

L
N

Master

Summary of Contents for compact office

Page 1: ...f learning characteristic i e the unit is able to automatically extend the switch off delay time to max 15min or reduce it to the minimum set time The switch off delay time will not be changed if it is set to 2 min or less Fully or Semi automatic Operation The compact office optionally allows fully automatic lighting control for more convenience or semi automatic control for better energy saving r...

Page 2: ...are present all the time If the con tact is closed the switch off delay time 10s 120min is restarted at each detection of movement Room Surveillance If the switch on delay is set to Surveillance the sensi tivity of the switched output for presence is reduced The contact closes in case of distinct move ments only and thus reliably indicates the presence of persons The switch off delay time remains ...

Page 3: ...rightness for indirect lighting on the site of installation must not exceed 2000Lux for brightness threshold 200Lux If the brightness threshold value is set to On the brightness measurement is deactivated no influence by brightness desired Suitable Lamps The compact office presence detector is designed for use with fluorescent lights FL PL as well as halogen incan descent lights The maximum number...

Page 4: ...vation of pulse function Switch off delay for presence HVAC surveillance Switch on delay for HVAC activation of room surveillance function DIP switches DIP1 Lighting control fully semi automatic DIP2 Push button function Room Corridor DIP3 Push button switch control DIP6 Operation mode normal operation test Mechanical safety lock The mechanical lock serves to secure the sensor module firmly on the...

Reviews: