Linienkoppler S KNX 

                                         

 

 
 

Status: March 16 (Subject to change)                                                                                         Page 

1

 of 

29

  

 

 

 

 

 
 
 
 
 

Line coupler S KNX 

 
 
 
 
 
 

 

 
 
 
 

 

 

 
 
 

Line coupler S KNX 

                                9070880 

Summary of Contents for 9070880

Page 1: ...Linienkoppler S KNX Status March 16 Subject to change Page 1 of 29 Line coupler S KNX Line coupler S KNX 9070880 ...

Page 2: ...ation 14 2 4 1 Display elements 15 3 Commissioning 16 3 1 Overview 16 3 2 Parameters 17 3 2 1 Application for ETS 4 17 3 2 1 1 Parameter window General 18 3 2 1 2 Device function Line Area Coupler 19 3 2 1 2 1 Parameter window Main line Line 19 3 2 1 2 2 Parameter window Line Main line 22 3 2 1 3 Device function Repeater 23 3 2 1 3 1 Parameter window Settings 23 3 2 2 Applications for the ETS 3 24...

Page 3: ...ct manual Application programs with different ranges of functions can be loaded in the line couple S For this reason all the parameters and functions for ETS 4 and also for ETS 3 are explained in chapter 3 Note Different application programs are available with the line coupler S for ETS 3 and ETS 4 Some of the functions for the ETS 4 are not available in the applications for the ETS 3 see Overview...

Page 4: ...ng examples Important These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury Caution These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury Danger These safety instructions are used if there is a danger for life and limb with inappropriate use Danger These safety instructions are used ...

Page 5: ...articularly during commissioning and for diagnostic purposes to set the option route for both parameters Group telegrams main group 0 13 and Group telegrams main group 14 31 i e the filter table is switched off If the system is fully in operation both parameters should be reset again to the standard values The Line Coupler S is then subsequently reprogrammed with the application Here the correct f...

Page 6: ... 0 Main Line Main line with up to 15 line couplers physical addres x y 0 Line Line with up to 64 devices including the line coupler Up to 256 devices are possible when up to three line repeaters are used The function of the device is assigned by the assignment of the physical address Note If a second output of the Power Supply SV S is used for connection a DV S choke must be connected For further ...

Page 7: ... KNX power supply The repeaters do not have filter tables For this reason a telegram is sent in all line segments independently of whether or not it is processed in the respective line segment Whether this telegram is initiated within the line or whether it has been sent from the main line via the repeater is also irrelevant If there is a transmission error of a physically addressed telegram this ...

Page 8: ... with up to 15 line couplers Line Line with up to three repeaters Line Segment Line segment per segment up to 64 devices are possible in total up to 256 devices are possible including the repeater Note The topology is not defined with the repeater Under the coupler 1 1 0 the addresses 1 1 0 to 1 1 255 can be assigned as required to the segments Line coupler S Line coupler S Line coupler S Line cou...

Page 9: ...urposes 2 1 Technical data Supply Rated voltage 21 31 V DC via the bus Power consumption Maximum 0 25 W Current consumption Maximum 12 mA Connections KNX subline 2 Line Via left bus connection terminal KNX subline 1 Main line Via right bus connection terminal Operating and display elements Button LED red For assignment of the physical address LED green For indicating operation LED yellow For indic...

Page 10: ...installation device MDRC Modular installation device Pro M Dimensions 90 x 36 x 64 5 mm H x W x D Mounting width 2 modules at 18 mm Mounting depth 64 5 mm Installation On 35 mm mounting rail To EN 60 715 Mounting position As required Weight without packaging 0 075 kg Housing colour Plastic housing grey Approval EN 60 669 1 EN 50 428 KNX certification EN 50 090 2 2 EN 50 491 CE mark In accordance w...

Page 11: ...u inhibit access to all devices of the project with a BCU code it has no effect on this device Data can still be read and programmed Note Different application programs are available with the Line coupler S for ETS 3 and ETS 4 Some of the functions for the ETS 4 are not available in the applications for the ETS 3 see Overview page 16 In ETS 3 there is a separate application for coupling and for re...

Page 12: ... Label carrier 2 Button Programming 3 LED Programming red 4 Bus connection terminal of the primary main line 5 Bus connection terminal of the secondary line 6 LED yellow 7 LED yellow 8 LED green Note The main and secondary lines must each be supplied with power from separate power sources electrically isolated 9070880 ...

Page 13: ...Line coupler S Device technology Status March 16 Subject to change Page 13 of 29 2 3 Dimension drawing Line coupler S 9070880 ...

Page 14: ...s regulations and specifications for your country should be observed when planning and setting up electrical installations and security systems for intrusion and fire detection Protect the device from damp dirt and damage during transport storage and operation Only operate the device within the specified technical data limits The device should only be operated in an enclosed housing distribution b...

Page 15: ...operation OFF The Line coupler S is not operational No power supply is applied or it has malfunctioned ON The Line coupler S is operational and is supplied by the main line The power supply is applied OFF No main line connected or voltage failure on the main line ON The main line is connected Flashes Telegram traffic on the main line OFF No line connected or voltage failure on the line ON A line i...

Page 16: ...USB or IP interface is required 3 1 Overview The following table provides an overview of the functions possible with the Line coupler S and the application programs Couple Repeat 2 x ETS 4 as well as Couple 1 x or Repeat 1 x ETS 3 Line Area Coupler properties ETS 3 ETS 4 Function Line Area Coupler Filter group telegrams main group 0 13 Filter group telegrams main group 14 31 Block physically addre...

Page 17: ... The following chapter describes the parameters of the Line coupler S using the parameter windows The parameter windows feature a dynamic structure so that further parameters may be enabled depending on the parameterization and the function The default values of the parameters are underlined e g Options yes no 3 2 1 Application for ETS 4 The application Couple Repeat 2 x with extended functional r...

Page 18: ...e Area Coupler Repeater Line Area Coupler The data flow between two lines is connected Both lines are electrically isolated from one another The Parameter window Main line Line page 19 and Parameter window Line Main line page 22 appear Repeater The data flow between two line segments is connected Both lines are electrically isolated from one another Parameter window Settings page 23 is enabled ...

Page 19: ...nection from the primary main line to the line are undertaken Group telegrams main group 0 13 Group telegrams main group 14 31 Option filter route block filter Only group telegrams entered into the filter table are routed The ETS automatically creates the filter table route All group telegrams are routed Block All group telegrams are blocked Physically addressed telegrams Option filter block filte...

Page 20: ...peated user defined The response can be set individually for different types of telegram Repeat group addressed telegrams Options yes no yes If an error is detected when a group addressed telegram is transmitted the telegram is repeated up to three times no The telegram is not repeated Repeat physically addressed telegrams Options yes no yes If an error is detected when a physically addressed tele...

Page 21: ...applies with a group address view Main groups 0 13 1 28 671 Main groups 14 31 28 672 65 535 NOTE In the ETS 4 it is possible to not just assign two or three stage group addresses it is possible to freely assign them If the free group address view is selected main group 0 13 corresponds to subgroup range 1 28 671 and main group 14 31 with subgroup range 28 672 65 535 Relevant details can be read wi...

Page 22: ...device function Line Area Coupler has been selected In this parameter window the telegram functions for the connection from a secondary line to the primary main line are defined The parameter setting of the connections Line Main line and Main line Line do not differentiate from one another The descriptions of the parameter setting options are described in Parameter window Main line Line page 19 ...

Page 23: ...e of errors repeat group addressed telegrams on main line Options yes no yes If an error is detected when a group addressed telegram is transmitted on the main line the telegram is repeated up to three times no The telegram is not repeated In case of errors repeat group addressed telegrams on line Options yes no yes If an error is detected when a group addressed telegram is transmitted on a line t...

Page 24: ... Couple 1 x parameter window Settings In this parameter window the settings for the Area Line Coupler are defined Group telegrams main group 0 13 Main line Line Group telegrams main group 0 13 Line Main line Option filter route block filter Only group telegrams entered into the filter table are routed The ETS automatically creates the filter table route All group telegrams are routed Block All gro...

Page 25: ...up addressed telegrams on main line In case of errors repeat group addressed telegrams on line Options yes no yes If an error is detected when a telegram is transmitted the telegram is repeated up to three times no The telegram is not repeated Telegram confirmation on Main Line Telegram confirmation on Line Options only if routed always only if routed Telegrams that are routed are acknowledged alw...

Page 26: ...up addressed telegrams on main line Options yes no yes If an error is detected when a group addressed telegram is transmitted on the main line the telegram is repeated up to three times no The telegram is not repeated In case of errors repeat group addressed telegrams on line Options yes no yes If an error is detected when a group addressed telegram is transmitted on a line the telegram is repeate...

Page 27: ... 29 A Appendix A 1 Scope of delivery The Theben AG Line coupler S is supplied together with the following components Please check the items received using the following list 1 x Line coupler S 1 x installation and operating instructions 2 x bus connection terminal red black ...

Page 28: ...Line coupler S Manual Status March 16 Subject to change Page 28 of 29 4 Manual ...

Page 29: ...Line coupler S Manual Status March 16 Subject to change Page 29 of 29 ...