8
Factory settings
The presence detector thePrema P360 DALI is supplied with
the following parameter values:
Parameters
Value
Brightness setpoint value A
300 lux
Room correction factor A
0.3
Switch-on dimming value
50 %
Time delay A
10 min
Short presence A
On
Energy saving mode
eco
Standby time
0
Standby brightness
10 %
Detection sensitivity
Increment 3
Group address
I
Scene 1
70 %
Scene 2
30 %
LED display motion
Off
Reset DALI EVGs
The connected DALI EVGs are reset to factory settings.
9. Start-up
Switch-on behaviour
Every time the sensor unit is inserted into the power supply
unit, or every time the power supply is switched on, the pre-
sence detector runs through two phases that are shown by an
LED:
1. Start-up phase (30 s)
•
The red LED flashes at one second intervals, lighting is
switched on at 70 %.
•
The detector does not react to button commands and to
user remote control „theSenda S“.
•
The lighting is switched off after 30 seconds when the
room is unoccupied.
2. Operation
•
In case of presence, the detector immediately dims to the
desired setpoint value. The red LED is off.
•
The detector is ready for operation.
Presence test
Presence test mode is used to test presence detection and
wiring. The presence test mode can be activated directly on
the presence detector via DIP switch, or with management
remote control „Sendo Pro 868 A“, or installation remote con-
trol „theSenda P“.
Setting presence test mode with DIP switch
Set DIP switch to “Test“ (in parallel switching with all
detectors).
run
test
1. Start-up phase (30 s)
During 30 s, the lighting is switched on at 100 %, and the red
LED indicates the test mode (20 s On, 10 s Off).
2. Operation
•
Every movement is indicated by the red LED, and the
lighting is switched on at 100 %.
•
If there is no motion, the red LED switches off, and the
lighting is switched off after 10 s.
•
Brightness measurement deactivated, detector does not
react to brightness.
•
The detector reacts as in configuration type fully auto
-
matic device, even if semi-automatic is set.
•
Detector stays permanently in the test phase.
Setting the presence test mode via remote control
•
The detector goes directly into test mode when the test
mode is set via the remote control:
•
Every movement is indicated by the red LED, and the
lighting is switched on at 100 %.
•
If there is no motion, the red LED switches off, and the
lighting is switched off after 10 s.
•
Brightness measurement deactivated, detector does not
react to brightness.
•
The detector reacts as in configuration type fully auto
-
matic device, even if semi-automatic is set.
•
Teach-in cannot be activated in test mode.
•
Test mode ends automatically after 10 min. The detector
performs a new start (see switch-on behaviour).
10. Technical Data
Operating voltage
230 V AC +10 %/-15 %
Frequency
50 Hz
Upstream protection device:
13 A
Power consumption
approx. 0.5 W
Type of installation
Ceiling installation; flush/
surface mounted or ceiling
installation
Installation height
2.0 – 3.5 m
Minimum height
> 1.7 m
Detection area
horizontal
vertical
360°
120°
Maximum range
5 x 5 m (Mh. 3.0 m)/25 m
2
seated
8 x 8 m (Mh. 3.5 m)/64 m
2
walking
Setting range brightness setpoint value
5 – 3000 lux
Lighting time delay
10 s – 60 min
Lighting standby time
0 s – 60 min/permanently on
Standby brightness
1 – 25 %
Control output lighting
50 mA/DALI interface in accor-
dance with EN 62386:2009 for
max. 25 DALI devices
Connection type
Screw terminals
Max. cable cross-section
max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 20 (IP 40 installed)
Ambient temperature
0 °C – 50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
directive 2014/30/EC and of
directive 2014/35/EC.