background image

1

thePrema S360 DALI UP WH

2070525

thePrema S360 DALI UP GR 

2070526

307184

1103077301

Presence detector

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Square detection area 360° (up to 64 m

2

) for reliable and 

easy planning

 

Automatic lighting control with constant lighting control 
or switching operation

 

Constant lighting control with standby function

 

Lighting dimmable in switching operation with standby 
function

 

Easy to start-up without programming group addresses 
(DALI Broadcast)

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs

 

Calibration of brightness measurement

 

Fully or semi-automatic operation, switchable

 

Brightness setpoint value adjustable in lux

 

Teach-in function via remote control or button

 

Self-learning time delay

 

Reduction of time delay when present briefly (short-term 

presence)

 

Detection sensitivity configurable

 

Connection option for buttons for manual dimming and 
switching 

 

Behaviour upon button operation selectable

 

Scene functionality

 

Ready for immediate use due to factory presetting

 

Exceptionally easy configuration of the energy-saving 

response with „eco plus“ function

 

Test mode for checking function and detection area

 

Extension of detection area via Master/Slave or Master/
Master switching

 

Ceiling installation in flush-mounted box

 

Surface mounting on ceilings possible with back box 
(option)

 

User remote control „theSenda S“ (option)

 

Management remote control „SendoPro“ (option)

 

Installation remote control „theSenda P“ (option)

2.  Safety

Danger of death through electric shock or fire!

 Installation should only be carried out by a quali-

fied electrician!

WARNING

 

Work on electrical systems may only be carried out by 

qualified electricians or by instructed persons under the 
guidance and supervision of a qualified electrician in 

accordance with the technical regulations applying to 
electricity! 

 

Comply with the country-specific safety regulations for 

work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated with any object, the guarantee lapses.

3.  Proper use

The presence detector is intended for interior installation. The 

presence detector is exclusively intended for the use as con-

tractually agreed between the manufacturer and the user. Any 

other use is considered to be unacceptable. The manufacturer 

does not accept liability for any resulting damages.

4.  Function

The presence detector is primarily used in offices, schools, 

conference rooms and corridors, as well as in homes, for easy 

and energy-efficient control of lighting. The lighting is accor

-

dingly influenced by switching or constant lighting control.

Function description

 Mixed light measurement 

 Presence detection

 Artificial light

 Button for manual lighting control

 Incident daylight

Settings on thePrema S360 DALI

 Brightness setpoint value (lux)

 Lighting time delay 

 Lighting standby time

 Standby brightness value

 DIP-Switch: 

 

DIP1 

Fully automatic device/semi-automatic

 

DIP2 

Constant lighting control: on/off

 

DIP3 

Response to manual override:  

 

 

school/office

 

DIP4 

Adjustment of the brightness setpoint value  

 

 

via button: on/off

 

DIP5 

Short-term presence: on/off

 

DIP6 

Operating mode: normal operation/presence  

 

 

test (walking test)

Summary of Contents for 2070525

Page 1: ...Safety Danger of death through electric shock or fire Installation should only be carried out by a quali fied electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the technical regulations applying to electricity Comply with the country specific safe...

Page 2: ...s to the standby brightness if the room brightness falls below the brightness setpoint value When the room is entered again the detector returns to the programmed brightness setpoint value either automatically fully automatic device or after the button is operated semi automatic device In switching operation the standby function is also available Instead of the brightness setpoint value the switch...

Page 3: ... 0 m 0 5 m 3 0 m 25 m2 5 0 m x 5 0 m 49 m2 7 0 m x 7 0 m 1 0 m 3 5 m 64 m2 8 0 m x 8 0 m 1 0 m Brightness measurement The presence detector measures artificial light and daylight opening angle for each approx 30 The installation loca tion is the reference point for the lighting level The bright ness measurement can be adapted to the conditions in a room with the room correction factor The light me...

Page 4: ...ments Delay times and brightness setpoint values are set individually on each Master Presence continues to be detected by all detectors L N L P S Master EVG DALI 1 DA DA L S Master EVG DALI 2 DA DA N P N One Master with individual brightness measurement per lighting group Set potentiometer and DIP switch individually for each Master Switch up to 10 detectors in parallel Use the phase with the same...

Page 5: ...ith the potentiometer the desired basic brightness in standby operation can be set The setting range is between 1 and 25 of the lamp output The factory presetting is at 10 1 3 5 10 15 20 25 By using the management remote control the standby set tings can be set in finer increments DIP switch Fully semi automatic device auto man auto man Description of the function semi automatic or fully automatic...

Page 6: ...ness is measured below the presence detector If the prevailing brightness is below the setpoint value the light is switched on when a presence is detected in configuration type fully automatic device Value range Lux values with SendoPro 868 A management remote control In the installation remote control theSenda P the following values are available The currently measured brightness value lux can be...

Page 7: ...lighting switches on and off automa tically due to presence absence and brightness auto Semi automatic Switching on always has to be done manually Switching off is done automatically by the presence detector due to presence or brightness man Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 By selecting the test presence operating mode the ...

Page 8: ...here is no motion the red LED switches off and the lighting is switched off after 10 s Brightness measurement deactivated detector does not react to brightness The detector reacts as in configuration type fully auto matic device even if semi automatic is set Detector stays permanently in the test phase Setting the presence test mode via remote control The detector goes directly into test mode when...

Page 9: ...detector Check wiring to the button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test Device not properly functional Guarantee Theben HTS presence detectors are manufactured with the utmost care and using state of the art technology and are quality tested T...

Page 10: ...eben de SendoPro 868 A Item No 9070675 Details www theben de theSenda S Item No 9070911 Details www theben de theSenda P Item No 9070910 Details www theben de 13 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch Addresses telephone numbers etc www theben hts ch ...