background image

WARNING: 

AC power must be off before proceeding with assembly or installation of emergency driver.

IMPORTANT:

 For use with non-dimming LED fixtures up to 12W. For use with LED fixtures(MAX 100W)

 that utilize 0-10V dimming that are above 12W, but this inverter will be limited to 12W(Including driver).

IMPORTANT: 

An un-switched AC power source of 100Vac to 347Vac is required. 

CAUTION: 

Make sure all electrical connections conform to the National Electrical Code and all 

applicable local regulations. 

CAUTION: 

Do not let power supply cords touch hot surfaces. 

CAUTION: 

Do not mount near gas or electric heaters.

CAUTION: 

Use with grounded, UL Listed, dry location rated fixtures.

CAUTION: 

The equipment is intended for ordinary locations and for permanent installation into one or 

more Listed emergency luminaires.

CAUTION:

 Battery is rechargeable Li-ion type and must be recycled or disposed of properly. 

Do not use this emergency driver with accessory equipment other than recommended by manufacturer; 
failure to follow this may cause an unsafe condition. Servicing should only be performed by qualified 
service personnel. Do not use this emergency driver for other than intended use. Not suitable for high-risk 
task area lighting. Equipment should be mounted in locations and at heights where it will not readily be 
subjected to tampering by unauthorized personnel.

IMPORTANT: 

Indicator (LED light) illuminated indicates battery in charge mode when AC power is 

applied. It is recommended and required by applicable code to test emergency LED Driver to ensure 
proper function of the system; push the test switch every thirty (30) days to ensure the emergency driver 
is functioning by illuminating the light source. Conduct a ninety (90) minutes discharge test one (1) time 
per year; LED light source should be illuminated for a minimum of ninety (90) minutes .

TESTING SYSTEM: 

 The emergency battery requires a charge minimum of one (1) hour before testing 

the circuit. A full charge requires twenty four (24 Hours) .

Risk

 

of

 

Electric

 

Shock

SAVE THESE INSTRUCTIONS

PLEASE READ CAREFULLY AND FOLLOW ALL 

INSTRUCTIONS FOR YOUR OWN SAFETY

When using electrical equipment and this lighting device 

basic safety precaution should be followed at all times 

including but not limited to the following:

IMPORTANT SAFEGUARDS

Disconnect power at fuse or  

circuit breaker before installing 

or servicing

Installation And Operation Instructions

WP-CEP-12C-200VPE

Summary of Contents for WP-CEP-12C-200VPE

Page 1: ...nel Do not use this emergency driver for other than intended use Not suitable for high risk task area lighting Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel IMPORTANT Indicator LED light illuminated indicates battery in charge mode when AC power is applied It is recommended and required by applicable code to te...

Page 2: ... luminaire manufacture This number will be given in lumens per watt lm w It is the installer s responsibility to validate the luminaire manufacturer s efficacy data This can be accomplished by direct measurement by review of independent 3rd party test data UL ETL etc accessing a public database of 3rd party data such as Design Lights Consortium www designlights org or other comparable means b Lume...

Page 3: ...n ON None LED OFF Flashing Green 1s on 1s off cycle Slow Flashing Green 5s on 5s off cycle Flashing Green 0 1s on 5s off cycle Enable the Self diagnostic test system Flashing Green 1s on 1s off 5 times System OK AC OK System NG battery voltage is too low LED fixture is Short Battery not detected check battery connection Discharge time is less than 90 minutes Self diagnostic test LED fixture is Ope...

Page 4: ...Wiring Diagram and Dimensions ...

Page 5: ......

Page 6: ... for typical installation and select appropriate mounting method Step 3 WIRING THE BACKUP INVERTER Use the wiring diagram found on page 4 as reference Connect the AC power source leads Switched and Unswitched to the input of the backup inverter Connect the output leads of backup inverter to the AC driver Wire the AC driver with the lamp in accordance with manufactures installation instructions Mak...

Page 7: ...Illustration 1 Illustration 2 ...

Reviews: