Make 3×35mm sink holes of installation hole size in the wall, insert the wall plug, and
then screw in M5X30 screws through the installation holes inside the EV Charging Box.
The power line is connected with a Type B Residual current circuit breaker, the single-
phase EV Charging Box is connected with N and L, and the three-phase EV Charging
Box is connected to N ,L1, L2 and L3. Ground wire (PE wire) is connected to the yellow
and green terminals.
4).
Current option and setting by DIP switch
WARNING:Installation and AMP settings are only to the carried out by a trained and
authorized electrical installer.
The current of the device is set to 32Amp as default factory setting
However, the rating can be adjusted to 10, 16, 20, 25, 32A via built-in DIP switch of
protocol controller as user request.
DIP switch setting for RFID version :
A
10
16
20
25
32
mm²
2.5
2.5
4
4
6
DIP
DIP
DIP
DIP
DIP
3).
Recommended cable section:
DIP switch setting for tethered cable and free/socket version :
LOST CARD
RFID