5.3 E1 (Indoor and outdoor unit communication error)
(only for
MWFOT24S
)
Description
: The indoor unit has not received feedback from the outdoor unit for 120 seconds.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
• Reactor
Troubleshooting and repair:
Power off, then restart the unit after 2 minutes.
Does a problem remain?
The unit is operating normally
NO
Measure Vs. (Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
YES
Is the voltage moving
alternately between Positive and
negative?
Check the outdoor wiring connection.
Is it normal?
NO
Replace the outdoor PCB.
Power on.
Is the error
resolved?
Replace the indoor PCB.
NO
Check the indoor wiring
connections
Is it normal?
Replace the indoor PCB.
Power on.
YES
Is the error resolved?
Replace the outdoor PCB.
NO
The voltage moves alternately with
positive value.
NO
The voltage is a
certain value
NO