5.7.2 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the monitor position display needs to be connected to power (red &
black) and to the communication link (blue & white) from the monitor. The cable exits the back side of the enclosure and can be installed
straight back thru an opening in a panel or laid into groove in enclosure for flush mounting. Refer to Figure 5.1.2 for typical cable
preparation.
Fig 5.7.1 - Monitor Position Display Hole Dimensions
5.7 MONITOR POSITION DISPLAY (Y4E-DISP)
The monitor position display is supplied with a 10' (3 m) long 4-conductor cable. The installer will need to surface mount the enclosure in
a dry area and connect the cable to power and the communication link of the monitor. Display is designed for use with 180° total
horizontal axis travel.
5.7.1 ENCLOSURE MOUNTING
Select proper location for display.
The
display is not weatherproof and needs to be
inside a protected area such as in the cab.
MOUNT ENCLOSURE WITH
(2) #10 FASTENERS.
TIGHTEN SECURELY.
5.8 REMOTE AUXILIARY INTERFACE BOX (YE-REMAUX)
Figure 5.8.1
Remote Aux. Interface Box Hole Dimensions
The Remote Auxiliary Interface Box allows a user to utilize the AUX1 and AUX2 buttons located on the monitor operator station or any
remote operator station. The Interface Box is equipped with two relays that can operate lights, interface to a valve controller or in some
cases operate a valve directly, etc. The contact rating of the relay is 16 amps @ 30VDC for resistive loads and 8 amps @ 30VDC for
inductive loads.
The installer will need to mount the interface box and connect the cable to power and the communication link of the monitor.
Select proper enclosure location. Enclosure is designed to be surface mounted and the size is 5” x 3 1/8” (127 x 80mm). Height of
enclosure is 2 3/8” (60mm). Refer to Figure 5.8.1 for mounting hole dimensions.
The Interface Box provides no overload protection for the device it is controlling. Failure to provide
overload protection will damage relay contacts, which will disable device being controlled.
WARNING
5.8.1 ENCLOSURE MOUNTING
See figure 5.0 for typical connections. The 4-conductor cable from the communication interface box needs to be connected to power
(red & black) and to the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation.
Each relay has one Form-C contact (common, normally open, normally closed) that can be used.
5.8.2 ELECTRICAL WIRING
MOUNT ENCLOSURE
WITH (2) 1/4-20 FASTENERS
TIGHTEN SECURELY.
4-1/2"
(114 mm)
2"
(51
mm)