background image

©Copyright Task Force Tips LLC  2012-2019 

LIB-065 August 30, 2019  Rev 01

5

2.4  NOZZLE COUPLINGS

NH (National Hose Threads per NFPA #1963) threads are standard on all nozzles. Other threads such as NPSH (National Pipe 
Straight Hose threads per ANSI/ASME #B1.20.7) can be specifi ed at time of order.

CAUTION

Nozzle must be properly connected. Mismatched or damaged threads may cause nozzle to leak 
or uncouple under pressure and could cause injury.

CAUTION

Do  not  couple  aluminum  to  brass.  Dissimilar  metals  coupled  together  can  cause  galvanic 
corrosion that can result in inability to unscrew threads or complete loss of thread engagement.

2.5 USE WITH SALT WATER

Use with salt water is permissible provided the nozzle is thoroughly cleaned with fresh water after each use. The service life of the 
nozzle may be shortened due to the eff ects of corrosion and is not covered under warranty.

2.6  USE WITH FOAM

Nozzles may be used with foam solutions. Refer to fi re service training for the proper use of foam.

WARNING

For Class B fi res, lack of foam or interruption in the foam stream can cause a break in the foam blanket 
and greatly increase the risk of injury or death. Assure that:  Application rate is suffi  cient (see NFPA 11 
or foam manufacturer’s recommendations); Enough concentrate is on hand to complete task (see NFPA 
for minimum duration time requirements); Foam logistics have been carefully planned. Allow for such 
things as:  Storage of foam in a location not exposed to the hazard it protects;  Personnel, equipment 
and technique to deliver foam at a rapid enough rate;  Removal of empty foam containers;  Keeping clear 
path to deliver foam as hoses, other equipment and vehicles are deployed.

WARNING

Improper use of foam can result in injury or damage to the environment. Follow foam manufacturer’s 
instructions and fi re service training to avoid:  Using wrong type of foam on a fi re, i.e. Class A foam on a 
Class B fi re;  Plunging foam into pools of burning liquid fuels;  Causing environmental damage;  Directing 
stream at personnel.

WARNING

There  is  a  wide  variety  of  foam  concentrates.  Each  user  is  responsible  for  verifying  that  any  foam 
concentrate chosen to be used with this unit has been tested to assure that the foam obtained is suitable 
for the purpose intended.

3.0  FLOW CHARACTERISTICS

Each Ultimatic ER nozzle has a pressure rating on the face of the baffl  e which can be seen by looking at the front end of the nozzle. 
Make sure that the pump system that is being used is capable of the fl ows and pressures of the selected Ultimatic ER Model. 
Automatic nozzles operate by sensing the pressure at the nozzle’s inlet and adjusting the discharge opening to maintain a constant 
pressure throughout the fl ow range of the nozzle. For example, when the pressure at the inlet increases, the exit area is automatically 
increased until the inlet pressure returns to the nominal pressure of the nozzle.

0

75

150

225

300

375

450

0

2

4

6

8

10

12

0

20

40

60

80

100

120

140

160

180

200

10

30

50

70

90

110

130

FLOW (LPM)

PR

ESSUR

(B

A

R

)

PR

ESSUR

(PSI)

FLOW (GPM)

ULTIMATIC ER NOZZLES - FLOW CURVES

B-TO-ERP-150:  10-125 gpm @ 150 psi (40-500 l/min @ 10 bar)

B-TO-ERP-120:  10-125 gpm @ 120 psi (40-500 l/min @ 8 bar)

B-TO-ERP:  10-125 gpm @ 100 psi (40-500 l/min @ 7 bar)

BL-TO-ERP:  10-100 gpm @ 75 psi (40-400 l/min @ 5 bar)

Fig 3.0

Summary of Contents for Ultimatic ER

Page 1: ...n who has not read and understood all operating and safety instructions is not qualified to operate the Ultimatic ER Nozzle Call 800 348 2686 with any questions This instruction manual is intended to familiarize firefighters and maintenance personnel with the operation servicing and safety procedures associated with the nozzle This manual should be kept available to all operating and maintenance pers...

Page 2: ...UESTIONS 10 9 0 MAINTENANCE 10 9 1 LUBRICATION 10 9 2 SERVICE TESTING 10 9 2 1 HYDROSTATIC TESTING 10 9 2 2 FLOW TESTING 11 9 2 3 RECORDS 11 9 3 REPAIR 11 10 0 INSPECTION CHECKLIST 12 Copyright Task Force Tips LLC 2008 2019 LIY 500 April 8 2019 Rev14 MANUAL Remote Control RC Monitor Electrical Controls Supplemental Instructions for use with RC Monitor Manual INSTRUCTIONS FOR INSTALLATION SAFE OPER...

Page 3: ...k to the nozzle will depend on the following factors Voltage of the line or equipment Distance from the nozzle to the line or equipment Size of the stream Whether the stream is solid or broken Purity of the water1 1 The Fire Fighter and Electrical Equipment The University of Michigan Extension Service Fourth Printing 1983 Page 47 CAUTION Fire streams are capable of injury and damage Do not direct ...

Page 4: ...efore use Obtain safety information at www tft com serial number WARNING PRODUCT LABEL Figure 2 1 Models and Terms 2 2 MECHANICAL SPECIFICATIONS Weight 6 4 lbs 2 9 kg Hydrostatic burst pressure minimum 1200 psi 83 bar Operating temperature range of fluid 33 to 120º F 1 to 50º C Storage temperature range 40 to 150º F 40 to 65º C Actuation Force 173 lbs 78 5 kg Speed Stream Fog 3 4 sec 3 4 sec Materi...

Page 5: ...am at a rapid enough rate Removal of empty foam containers Keeping clear path to deliver foam as hoses other equipment and vehicles are deployed WARNING Improper use of foam can result in injury or damage to the environment Follow foam manufacturer s instructions and fire service training to avoid Using wrong type of foam on a fire i e Class A foam on a Class B fire Plunging foam into pools of burnin...

Page 6: ...10 25 50 75 GPM FLOW LPM FLOW 38 95 190 284 LBS REACTION 3 10 23 36 26 69 84 91 E 100 53 110 PSI INLET PRESSURE KGF REACTION 1 4 4 5 10 4 16 3 KGF CM 2 INLET PRESSURE 1 8 4 8 4 1 6 4 E 379 24 0 7 7 F 125 70 122 E 473 31 8 8 6 100 PSI ELECTRIC REMOTE CONTROL NOZZLE 60 50 40 40 30 20 20 10 0 0 80 100 120 140 A B C D E F These trajectories reach and reaction numbers are provided for reference All dat...

Page 7: ... CURVE 10 25 50 75 GPM FLOW LPM FLOW 38 95 190 284 LBS REACTION 3 13 31 49 27 90 135 151 E 100 68 165 PSI INLET PRESSURE KGF REACTION 1 4 5 9 14 0 22 2 KGF CM 2 INLET PRESSURE 1 9 6 3 9 5 10 6 E 379 30 9 11 6 F 125 87 175 F 473 39 5 12 3 150 PSI ELECTRIC REMOTE CONTROL NOZZLE 60 50 40 40 30 20 20 10 0 0 80 100 120 140 A B C D E F These trajectories reach and reaction numbers are provided for refer...

Page 8: ...uring flush the nozzle reaction decreases as the pattern becomes wider and the pressure drops The nozzle reaction increases when returning the nozzle from the flush position When used with a TFT RC Monitor equipped with Smart Stream technology the Fog button must be pressed and held a second time to reach the Flush position after having reached Full Fog The purpose of the Smart Stream feature is to ...

Page 9: ...I 1 B820 ER 100 BARREL SUB ASS 120 PSI 1 B820 ER 120 BARREL SUB ASS 150 PSI 1 B820 ER 150 12 BARREL LABEL BLUE 1 B740 BARREL LABEL RED 1 B740 RED INDEX DESCRIPTION QTY PART NUMBER 13 O RING 030 1 VO 030 14 VALVE PLUG 1 B590 15 O RING 109 1 VO 109 16 I O SCREW 1 B595 17 7 32 TORLON BALL 4 V2130 TORLON 18 ER SHAPER GUIDE 1 B514 19 NAME LABEL BLUE 75 PSI 1 B745F NAME LABEL RED 100 PSI 1 B745 NAME LAB...

Page 10: ...een repaired or altered by someone else THIS IS A LIMITED EXPRESS WARRANTY ONLY TFT EXPRESSLY DISCLAIMS WITH RESPECT TO THE EQUIPMENT ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE THERE IS NO WARRANTY OF ANY NATURE MADE BY TFT BEYOND THAT STATED IN THIS DOCUMENT This limited warranty gives you specific legal rights and you may also have oth...

Page 11: ...ire hose couplings nozzles and fire hose appliances 2013 ed Section 5 5 4 Quincy MA National Fire Protection Agency 9 3 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced nozzles are repaired by experienced technicians to original specifications fully wet tested and promptly returned Repair charges for non warranty items are minimal Any re...

Page 12: ...tion if applicable 9 There is no damage to the nozzle tip 10 The shut off valve if so equipped operates as designed and shuts the flow off completely BEFORE BEING PLACED BACK IN SERVICE nozzles must be inspected to this checklist 1 All controls and adjustments are operational 2 Shut off valve if so equipped closes off the flow completely 3 There are no broken or missing parts 4 There is no damage to the...

Reviews: