Pagina 12 di 36
AD800E-STD.EN-06 - Subject to change without notice
TFT DryAir
sloped to prevent any return of condensate inside the dehumidifier.
If the channel of the moist air is very
long or needs to be upwards, realize a drainage hole of 5 mm at the lowest point of the discharge
channel.
It must be installed an air flow regulation damper.
Protect the channel output with a grid.
If
there is a risk that the temperature external to the conduit is very low, it is mandatory to insulate piping
to prevent the formation of condensation inside the duct.
Horizontal
Vertical
Expulsion
Expulsion
1.
Slop down
2.
Vertical expulsion of moist air
3.
Wire mesh
4.
Condensate drainage
Specifications for the input channel of reactivation air
This channel must be as short as possible. To prevent the entry of foreign bodies, protect the entrance
channel with a grid. It is not necessary to isolate the pipe, which may be inclined downwards. In some
installations, the reactivation air can be aspired from the room where the dehumidifier is installed and
in this case it is not necessary any channel.
It is advisable to install a damper on the reactivation circuit to allow a proper air flow calibration.
Specifications for the channels of process air and dry air in case the dehumidifier is installed
inside the room to be dehumidified
In this case, it’s not necessary the addiction of aspiration channels for the process air; the installation of
a protective grille is only required. The dry air produced must be ducted for the distribution inside the
dehumidified room.
Specifications for the channels of process air and dry air in case the dehumidifier is installed
outside the room to be dehumidified
In this case normally the inlet and outlet are channeled.
When the suction of air takes place from the outside, the outlet of the air duct must be at a sufficient
height above ground level in order to prevent the suction of slag and dust.
The air intake must be