When installing the iD loop it is usually more practical to run several cables from
the expander module to the different areas of protection. This effectively reduces
any distance problems and makes fault finding much easier.
To reduce the risk of induced interference and wherever possible, cables should
not be positioned along side mains power, telephone or other data transmission
cables, or run within the same ducting or trunking as any other cables.
The wiring for the system’s internal sounders (loudspeakers) should not be
connected in the same multi-core as the iD loop.
N
The 60IXD expander module is supplied with 4 off 10nF capacitors in the
spares pack. It is recommended that you connect a 10nF capacitor approximately
at the half way point of each iD spur. It is especially important to do this on iD
spurs that are less than 30 metres.
ID Biscuit Connections
The figure below shows both the old and newer iD Plus biscuits: