Eliwell ICPlus 915 Controller
TEMPERATURE CONTROL (Do not set the controller below 4°C.)
The SET temperature is factory set at 12°C.
The digital display normally displays return air temperature
.
To change the SET temperature,
press the SET button. If no alarms are
active, the ‘SP1’ label appears.
Press SET button again, the setpoint value appears on the display.
To change the Setpoint value
, press the and keys within 15 seconds.
Press SET to confirm the
modification.
The display will revert to the return air temperature after 15 seconds.
The fitted de-ice thermostat will activate a de-ice cycle when there is a
build up of ice on the evaporator
coil.
cCellarators will only heat a room if the electric heater option is fitted.
WARNING
The following actions could damage your system:
1.
Switching the unit OFF and ON quickly.
2.
Setting the unit to Heat and then back to cool quickly.
NB.
Allow at least 3 minutes between the above actions.
MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is
capable of supporting the unit weight
.
Leave space around the unit for air
circulation and access for installation and maintenance.
Dimensions in mm.
1500 min air off
100 min
100 min
600 min
CKC PIPEWORK
CKC INSTALLATION
12°C
– 23°C
«
«