Automatic boiler for wood pellets
65
Possible causes
Elimination
Performed by
blocked nozzles in the burner
clean the burner as prescribed annual review
service
dirty heat exchanger
clean heat exchanger
service
insufficient or reverse draft in the
chimney
solution is suggested by professional company
chimney service
Commissioning:
Is entitled to a professionally trained person.
9.7
ERROR FROM LOW TEMPERATURE OF WATER OR COMBUSTION PRODUCTS
During automatic operation is outlet water temperature continuously tested.
If the boiler can not reach the temperature of 40 ° C within 30 min. after switching from STAND -BY to automatic
operation or when the water temperature drops during operation below 40 ° C for longer than 30 minutes, the
control unit evaluates the situation as substandard condition and operation of the boiler is stopped.
This is indicated on the display with:
Stop-non ignition
Possible causes
Elimination
Performed by
low quality fuel
check fuel by specialist company, if
necessary, change the fuel
user
lack of fuel
replenish pellets in the fuel bin and fill
the transport route by manual override
of the feeders
user
impassable transport path, etc.
check and remove obstacles which
hinder the entry of fuel into the feeder
user
insufficient boiler output
increase the output
(max. up to nominal output)
user
wrong choice of boiler output
check the size of the heating system and
boiler output, preferably by a specialist
company
installation company
Commissioning:
Check the burner, remove the residue fuel or ash, run START.
9.8
ERROR OF TEMPERATURE SENSOR CONTACT
The control unit automatically detects the the operation of temperature sensors. In case of failure of the sensor
CU will display an error of specific sensor.
If CU loses contact with temperature sensor and the error persists, it is indicated on the display through the
message "ERROR TEMP.SENS".
Possible causes
Elimination
Performed by
defective sensor
replace the sensor
service
defective connection to the temperature
sensor
control of wiring, repair connections
service
Summary of Contents for KP 12-ES
Page 21: ...Automatic boiler for wood pellets 20 Picture No 15 Jacketing KP 22S KP 22 ES ...
Page 22: ...Automatic boiler for wood pellets 21 Picture No 16 Jacketing KP 62S KP 62 ES ...
Page 43: ...Automatic boiler for wood pellets 42 9 3 1 2Menu users settings ...
Page 45: ...Automatic boiler for wood pellets 44 Cleaning an ash removeing Skin Time window setting ...
Page 48: ...Automatic boiler for wood pellets 47 Actual values Configuration ...
Page 54: ...Automatic boiler for wood pellets 53 Cleaning Ash removing USB Time window setting ...
Page 55: ...Automatic boiler for wood pellets 54 Load from USB Save on USB ...
Page 60: ...Automatic boiler for wood pellets 59 ...
Page 62: ...Automatic boiler for wood pellets 61 ...
Page 63: ...Automatic boiler for wood pellets 62 i ...
Page 70: ...69 Picture No 31 Principle of the modulation ...
Page 72: ...71 Picture No 33 Directory information consuption wood pellets for boiler family KP ...
Page 73: ...72 Picture No 34 Circuit diagram control unit ...
Page 74: ...73 Picture No 35 Circuit diagram modul HZS 533 ...
Page 75: ...74 Picture No 36 Circuit diagram HZS 533 HZS 535 ...