8 Using the product 

15 

Manifold control keys 

 

Symbol 

Meaning 

 

 

-  Open menu 
-  Confirm input 
-  Switch on the display illumination: 

Press and hold the key for >2s 

-  Switch off the display illumination: 

Press and hold the key for >2s 

 

 / 

 

Change/navigate the display screen. 

 

 

-  Switches to the measurement view 
-  Back to the menu 
-  Switch off the instrument: Press 

and hold the key for >2s 

 

 

8.2 

Connecting the instruments 

 

 

Before each use, make sure that the refrigerant hoses are in flawless 
condition. 

Observe the system's maximum permitted operating pressure. 

 

 

Do not switch on the testo Smart Valve until all hoses have been 
attached and the installation is ready for charging. 

 

 

Protect the testo Smart Valve from vibrations. Otherwise, safe opening 
and closing cannot be guaranteed. 

If the testo Smart Valve is subjected to a hard impact or a fall, it must 
be switched on and off again. Otherwise, the valve position may be lost. 

 

✓ 

All connections must be pressureless (ambient pressure). 

 

Place refrigerant bottle on scale. 

 

 

Make sure that there is always enough refrigerant in the bottle so that 
the charging process can be carried out correctly. 

 

Connect refrigerant bottle to valve. 

 

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for 0560 5600

Page 1: ...testo 560i and testo Smart Valve 0564 1560 0560 5600 Instruction manual www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 2: ...www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 3: ...Switching off 12 8 Using the product 13 8 1 Control via manifold 14 8 2 Connecting the instruments 15 8 3 Manual charging via weight 16 8 4 Automatic charging by target weight 18 8 5 Automatic chargi...

Page 4: ...eeping connections clean 41 9 4 Removing oil residues 41 9 5 Ensuring measuring accuracy 41 9 6 Changing batteries 42 10 Technical data 43 10 1 Technical data for testo 560i 43 10 2 Technical data for...

Page 5: ...ord Warning Serious physical injury may occur Caution Minor physical injury or damage to the equipment may occur Careful Possible damage to equipment Implement the specified precautionary measures 1 2...

Page 6: ...harm the environment Please note the applicable environmental regulations Use with A2L refrigerants Testo measuring instruments as of July 2020 can be used in compliance with the prescribed laws stan...

Page 7: ...s When charging with liquid refrigerant an evaporation adapter must be used to protect the compressor or the flow rate limited via the manifold ATTENTION Charging liquid refrigerant too quickly can da...

Page 8: ...Product description 6 1 Overview of testo 560i 1 On off switch 2 Battery compartment on rear Symbol explanation Observe operating instructions www GlobalTestSupply com Find Quality Products Online at...

Page 9: ...nt hoses with quick release fitting passage can be closed via valve positioner 6 Refrigerant inlet Connection 7 16 UNF brass For refrigerant hoses with quick release fitting passage can be closed via...

Page 10: ...nserting batteries in the testo 560i 1 Open battery compartment 2 Insert the batteries scope of delivery into the battery compartment Observe the polarity 3 Close the battery compartment After inserti...

Page 11: ...ion can be established to the testo Smart App or to a testo 550s or testo 557s manifold Do not change or remove batteries during operation otherwise the charging process will be interrupted When not i...

Page 12: ...g a Bluetooth connection to the testo Smart App To establish a connection via Bluetooth you need a tablet or smartphone with the Testo Smart App already installed on it You can obtain the app for iOS...

Page 13: ...ooth and Menu Enter to confirm The Bluetooth menu is displayed 7 3 2 1 Switching on The Bluetooth menu is selected 1 Menu Enter In the On Off switch icon is displayed 2 Enable Bluetooth Use to activat...

Page 14: ...connection mode 7 3 2 2 Switching off The Bluetooth menu is activated 1 Menu Enter In the On Off switch icon is displayed 3 Disable Bluetooth Use to activate the Completed button and Menu Enter to co...

Page 15: ...iquid refrigerant slowly It is necessary to enter the maximum capacity of the system to prevent overcharging If unsure of total charge and information about the system is unavailable reclaim all refri...

Page 16: ...s and controls are implemented via the manifold Manifold main menu Measuring mode Refrigeration Evacuation System Leak Test Target Superheat Compressor Test DLT Delta T Refrigerant Filling Bluetooth C...

Page 17: ...ting pressure Do not switch on the testo Smart Valve until all hoses have been attached and the installation is ready for charging Protect the testo Smart Valve from vibrations Otherwise safe opening...

Page 18: ...ion with the app or testo 550s testo 557s manifold By manually opening and closing the refrigerant bottle valve the system is charged with refrigerant until the target value weight superheating subcoo...

Page 19: ...lly and add refrigerant to the system until the required value is reached Charging manually means the user will need to control the charge by opening and closing valves with a manifold or other valves...

Page 20: ...that the refrigerant hoses are in flawless condition and applied to all ports tight to prevent leaks The system must be supervised by a competent person throughout the entire process testo 560i and te...

Page 21: ...gerant and select if pulsed charging is desired on off Pulsed charging means that the valve opens and closes several times and the desired amount is thus filled in several small steps www GlobalTestSu...

Page 22: ...T CHARGE to start the process The valve opens and attempts to fill with the set charge quantity No pulsating charging takes place Added refrigerant is displayed in g kg increments on the manifold app...

Page 23: ...e product 21 4 Once charging is finished the process can be repeated NEW or another mode for charging OPTIMIZE can be selected www GlobalTestSupply com Find Quality Products Online at sales GlobalTest...

Page 24: ...red on the manifold app Based on the specified system size the algorithm creates a maximum weight to be filled When this maximum weight is reached automatic filling is paused and must be restarted Thi...

Page 25: ...8 Using the product 23 2 In the manifold app select the proper refrigerant and enter the maximum system charge www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 26: ...anifold app and hit START CHARGE to start the process The valve opens and attempts to reach the set superheat by charging refrigerant Added refrigerant is displayed in g kg increments on the manifold...

Page 27: ...s in second screen mode All settings must be made on the manifold Based on the specified system size the algorithm creates a maximum weight to be filled When this maximum weight is reached automatic f...

Page 28: ...8 Using the product 26 2 In the manifold app select the proper refrigerant and enter the maximum system charge www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 29: ...anifold app and hit START CHARGE to start the process The valve opens and attempts to reach the set subcooling by charging refrigerant Added refrigerant is displayed in g kg increments on the manifold...

Page 30: ...tem must be entered on the manifold app Based on the specified system size the algorithm creates a maximum weight to be filled When this maximum weight is reached automatic filling is paused and must...

Page 31: ...605i smart probes one to outdoor dry bulb and the other to indoor wet bulb Place two 605i smart probes to there corresponding locations as configured Press OK and a target superheat value will be calc...

Page 32: ...the process Refrigerant is automatically supplied to the system until the set value is reached Added refrigerant is displayed in g kg increments on the manifold app 8 Add another purging section to cl...

Page 33: ...valve to the closed position Purge the lines by pressing the valve on off button 3 times until all refrigerant has been clear of the lines into the system www GlobalTestSupply com Find Quality Product...

Page 34: ...Settings and controls are implemented via the app 1 Open main menu 2 Display of the measurement period 3 Display of the maximum system charging 4 Reading for each probe 5 Can be controlled with differ...

Page 35: ...formation Display report Multiple selection The Main menu can be accessed via the icon at top left To exit the main menu select a menu or right click on the guided menus The last screen displayed is s...

Page 36: ...mandatory Without any information in this field no customers or measuring sites can be stored 1 Click on Main menu opens 2 Click on Customer The Customer menu opens 3 Click on New Customer A new cust...

Page 37: ...u opens 3 Click on New Customer 4 Click on right tab Measuring Points 5 Click on New Measuring Point A new measuring point can be created 6 Store all relevant measuring site information 7 Click on rig...

Page 38: ...rview of the measurement results is displayed In the Memory menu all stored measurements are sorted by date and time Searching The Memory menu is open 1 Click on Search field with measurements opens 2...

Page 39: ...tion about currently connected probes as well as recently connected probes 8 8 4 1 Information Information is stored for each probe The app is connected to testo 550s testo 557s 1 Click on Main menu o...

Page 40: ...ns 3 Click on one of the displayed probes 4 Click on the Settings tab 5 Click on one of the displayed probes Settings appear that can be changed if necessary 8 8 5 Language 1 Click on Settings The Set...

Page 41: ...Settings The Settings menu opens 2 Click on Company details A window with company details opens 3 Click on the required data and enter if necessary The required company details are set 4 Exit Company...

Page 42: ...on and update are displayed for the connected instrument Automatic updates for instruments can be enabled or disabled Use the slider to activate or deactivate Update for connected instruments 8 8 9 2...

Page 43: ...y clean it with a damp cloth Connect high pressure air and use the function to click 3 times the button and the valve will open for 1 s This can help to remove small dust inside the valve 9 3 Keeping...

Page 44: ...ss will be interrupted When not in use for a long period Take out the batteries Changing the batteries in the testo Smart Valve The instrument is switched off 1 Unfold the suspension hook and open the...

Page 45: ...x 287 x 58 mm Ambient conditions Operating temperature 10 to 50 C 14 to 122 F Storage temperature 10 to 50 C 14 to 122 F Humidity in area of use 10 90 RH Measuring range 0 00 to 100 00 kg Accuracy no...

Page 46: ...tions in an open area Max permitted operating pressure 35 bar 11 Tips and assistance 11 1 Accessories Description Order no Magnetic strap for valve 0564 1001 For a complete list of all accessories and...

Page 47: ...www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 48: ...0970 5610 en 02 06 2022 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Reviews: