8.3.4 Modem connection cables
A standard modem connection cable is used to connect SM to a PC. This cable is required if an external mo-
dem is used, but instead if an internal modem is used then no need for this cable.
The connection cable between the UPS and DM must as follows:
UPS DB9 Pin
MODEM
DB25 Male
6
3
7
7
9
2
8.4 UPS Remote monitoring panel connection
Remote monitoring panel is used to monitor the UPS from 400m distance. This panel is installed to con-
trol/monitor room. If the distance is less than 25m then RS232 cable is used, and RS485 for larger distances.
Additional adaptor is required for RS485.
The remote monitoring panel transfers the data to the user from the UPS. The remote monitoring panel re-
quires 220Vac 50Hz AC voltage to operate, and it is better to use the output of the ups as a power supply.