9
STORAGE
If the STS is not to be installed immediately, it must be stored in its original packing and be shielded from
humidity and bad weather. The storage room must have the following characteristics:
Temperature:
Relative humidity
-10° ÷ +50°C
90% max
INSTALLATION ENVIRONMENT
Follow these recommendations when choosing the installation environment:
- avoid dusty areas
- confirm that the floor can support the weight of the STS
- avoid rooms that are too small and would prevent normal maintenance operations
- relative humidity at 20°C must not be greater than 90° non-condensing
- avoid placing the device in a position exposed to direct sunlight or hot air
- verify that the ambient temperature, with the STS in operation, is less than:
operating temperature:
maximum temperature for 8 hours/day:
average temperature over 24 hours:
0 ÷ +40°C
+ 40°C
+ 35°C
In order to maintain the temperature of the operating environment as specified above, it may be necessary to
install a means of removing the heat dissipated by the STS.
PRELIMINARY OPERATIONS
PACKING CASE CHECK
When the STS is delivered confirm that the packing case has not been damaged during transportation.
Be careful when removing the packing case to avoid scratching the STS cabinet.
The device must be handled carefully: any knocks or falls may damage it.
CONTENTS CHECK
The following item must be included inside the packing case.
•
Operating Manual
•
Test report
•
STS MANAGER
software, CD-ROM with the Software for remote STS management
" STS Manager Software"
•
CC05
Cable
POSITIONING
The air used to cool the STS is drawn in through the grills located on the lower part of the front door and exits
through the fan grills located on the top.
When positioning the STS keep in mind that:
• the space in front of the device should be free of obstacles for a distance of at least one metre to
permit maintenance operations
• in the back part of the device should be a free space of at least 50 cm between the rear of the device
and the wall to permit maintenance operations
• there should be a free space of at least 60 cm between the top of the device and the ceiling to permit
proper dissipation of exhaust air from the fans