4
www.tescom-ups.gr
NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
Batteries
Battery type
Sealed lead acid maintenance free battery
DC voltage
24 V
36 V
36 V
48 V
72 V
72 V
72 V
96 V
96 V
Inbuilt battery
12 V / 9
Ah
12 V / 7
Ah
/
12 V / 9
Ah
12 V / 7
Ah
/
12 V /
9 Ah
12 V / 7
Ah
/
Quantity
2
3
3
4
6
6
6
8
8
Charger output voltage
27.1
±
0.4
40.7
±
0.6
40.7
±
0.6
54.2
±
0.8
81.3
±
1.2
81.3
±
1.2
81.3
±
1.2
108.4
±
1.6
108.4
±
1.6
Recharging time
Recover 90% capacity in 3 hours for standard models
Charging current
(Max.)
Standard model: 1 A
Long time model: 6A /12A
System Control and Communications
Protections
Over-temp protection; Fan testing protection; Overload protection; Output
short circuit protection; Battery discharge protection
Communication port
Standard: RS232; Options: USB, SNMP card, dry contacts
Display
LCD
Environmental
Operating humidity
0 ~ 90 % RH @ 0 ~
40°C
(non-condensing)
Storage temperature
-
25°C
~
55°C(exclude
batteries)
Operating altitude
≤
1000m, above 1000m, derate 1% for each rising 100m
Protection class
IP20
Noise level
≤50dB
(at 1m)
Others
Dimensions (mm)
W ×
D
×
H
440
×
468
×
88
440
×
658
×
88
440
×
468
×
88
440
×
658
×
88
440
×
468
×
88
Weight (kg)
12.26 13.78
7.58
22.73 25.86
9.66
29.26
9.45 10.04
* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
Note
:
Model
Type
Model
Type
1kVA S(T)
1 kVA Standard model
1kVA XL(T)
1 kVA Long backup model
2kVA S(T)
2 kVA Standard model
2kVA XL(T)
2 kVA Long backup model
3kVA S(T)
3 kVA Standard model
3kVA XL(T)
3 kVA Long backup model