18

 
 

Problem

 

Possible cause

 

Solution 

 

The Fault code is 
“08”, and the 
buzzer beeps 
continuously. 

The UPS transfers to fault 
mode due to internal overheat. 

Make sure the UPS is not overloaded; the 
air vents are not blocked and the ambient 
temperature is not too high.Wait for   
10 minutes for the UPS to cool down before 
turning on again. If failed, please contact 
the distributor or service center. 

The Fault code is 
“09”, and the 
buzzer beeps 
continuously. 

The UPS output is 
short circuited. 

Remove all the loads. Turn off the UPS. 
Ensure that the load is not failed or the UPS 
has no internal faults before turning it on 
again. If failed, please contact the distributor 
or service center. 

The Fault code is 
“05” or “06”, the 
UPS beeps 
continuously. 

The UPS transfers to 
fault mode due to its 
internal fault. 

Please contact the distributor or 
service center. 

The Mode code is 
“03”, UPS turn into 
Battery mode. 

The voltage or 
frequency of the utility 
power is out of the 
input range of the UPS. 

The UPS is running in Battery mode. To 
save your data and close the application 
program. Make sure the utility power is 
within the input voltage or frequency range 
permitted by the UPS. 

The Fault code is 
“07”, the UPS 
beeps continuously. 

The UPS is 
overloaded or the 
load equipment is 
faulty. 

Check the loads and remove all   
no-critical equipment. Recalculate the   
load power and reduce the number of   
loads connected to the UPS.   
Check that the loads are not failed. 

The Warning code is “13”, the 
buzzer beeps every 
second. 

The charger of the 
UPS is defective. 

Please contact the distributor or 
service center. 

 
 
 

10. Operating mode for all models 
 

The different codes could be displayed on the LCD screen corresponding to their own operating modes, and 
they are illustrated as the follow: 
 
 
 

Operating mode

 

Code

 

Operating mode

 

Code 

Mode Code Table 

Parallel Mode 

02 

Battery mode 

03 

Bypass mode 

01 

Battery test mode 

04 

Line mode 

02 

 

 

Warning Code Table 

ID Loss 

21 

Charger Bad 

13 

Fan Error 

10 

IP Fuse Open 

11 

Battery Low 

12 

 

 

Fault Code Table 

Bus Fault 

05 

Inverter Fault 

06 

Overload Fault 

07 

Over temperature Fault 

08 

Other 

09 

 

15 

 
 
 
 

Summary of Contents for NEOLINE 6-20KVA UPS

Page 1: ...NEOLINE 6 20KVA UPS High Frequency Online UPS Uninterruptible Power System USER MANUAL...

Page 2: ...th all warnings and operating instructions in this manual and on the unit strictly Save this manual properly Do not operate this unit before reading through all safety information and operating instru...

Page 3: ...packing and inspection 9 4 2 Input and output power cords and protective earth groundins tallation 9 4 2 1 Notes for installation 9 4 2 2 Installation 9 4 3 Opertaing procedure for connecting the lon...

Page 4: ......

Page 5: ...nts further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation An appropriate disconnect device as short circuit backup protection should be...

Page 6: ...Verify that no voltage is present before servicing Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessar...

Page 7: ...IEC EN 62040 2 Category C3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 Level 4 Low Frequency Signals IEC EN 61000 2 2 Warning This is...

Page 8: ...4 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Page 9: ...E 106 Single phase inbuilt 10KVA NEOLINE 110 Single phase inbuilt Long back up time 10KVA NEOLINE 210 Three phase inbuilt 6KVA NEOLINE 106XL Single phase External battery bank 10KVA NEOLINE 110XL Sing...

Page 10: ...0 8 Synchronized 46 54Hz in Line mode AC mode 1 of normal frequency in Battery mode THD 2 Full load Linear load 105 125 load transfers to bypass mode after 1minutes 130 load transfers to bypass mode a...

Page 11: ...Select Button if the ups system is in bypass mode or self test mode the output frequency could be selected by pressing Select button and confirmed by pressing Enter button Enter Button if the ups sys...

Page 12: ...and the OVER LOAD lighting with warning it means ups in overload Indicates ups input voltage value output voltage value output frequency value which could be displayed from 0 to 999VAC The four items...

Page 13: ...and wiring must be performed in accordance with the local electric code and the following instructions by Professional personnel or safety please cut off the mains power switch before installation Th...

Page 14: ...onnection and finally turn on the loads one by one 10 No matter the UPS is connected to the utility power or not the output of the UPS may have electricity The parts inside the unit may still have haz...

Page 15: ...be not less than the data specified in the general specification as follow Model NEOLINE 106 NEOLINE 106XL NEOLINE 110 NEOLINE 110XL NEOLINE 210 NEOLINE 210XL NEOLINE 215XL NEOLINE 220XL Battery volta...

Page 16: ...equipped with battery individually 5 Please refer the figure followed to see the wiring of parallel operation The capacity of the breaker must be not less than the specification as follow Model No Ca...

Page 17: ...13 Parallel Installation Diagram 4 To perform the maintenance follow the stand alone requirement...

Page 18: ...14...

Page 19: ...15...

Page 20: ...OFF button continuously for more than 1 second and the buzzer will beep once The UPS will turn into Bypass mode 2 Upon completion of the above to turn it off output of electric current of the UPS is...

Page 21: ...ry to replace any connection cables please purchase the original materials from the authorized distributors or service centers so as to avoid overheat or spark resulting in fire due to insufficient ca...

Page 22: ...t of the input range of the UPS The UPS is running in Battery mode To save your data and close the application program Make sure the utility power is within the input voltage or frequency range permit...

Page 23: ...ss mode Bypass mode 10 2 Line mode The LCD display in Line mode is shown in the following diagram The information about the utility power the battery the temperature and load could be displayed The op...

Page 24: ...S is running in Battery mode the buzzer beeps once every 4 seconds If the ENTER button on the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Battery m...

Page 25: ...the following diagram When the UPS operating in parallel mode the operating mode code of the UPS is P2 Parallel mode 10 6 Warning mode The LCD display in warning mode is shown in the following diagra...

Page 26: ...n fault is shown in the following diagram The symbol MODE not be shown and the symbol FAULT is shown instead in code display Fault mode Bus Fault 10 8 Set Mode The LCD display in voltage set is shown...

Page 27: ...ollowing diagram 10 9 Battery Low voltage warning The LCD display in Battery Low voltage warning is shown in the following diagram Notice When Battery low voltage or short back up time both low voltag...

Page 28: ...y Low voltage warning is shown in the following diagram Note The above all diagrams temperature battery voltage Input voltage input frequency output voltage output frequency would alternately displaye...

Page 29: ...for further information 11 3 AS400 Interface Option Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Plea...

Page 30: ...onitoring software which provides userfriendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this sof...

Page 31: ...27 Appendix1 Rear Panel BACK VIEW of NEOLINE 106 NEOLINE 110...

Page 32: ...VIEW of NEOLINE 210XL NEOLINE 215XL NEOLINE 220XL BACK VIEW of NEOLINE 210 1 RS232 2 Inteligent Solt 3 Fan 4 Parallel Port 5 Input Breaker 6 Maintain Switch 7 Terminal Block Cover 8 Cable Rack 9 EPO...

Page 33: ...29 192321142002001...

Page 34: ...30 AGKK10360 10 2019...

Reviews: