54
831 Status code
Status
Inverter warning
Description
SLAVE UPS L1 phase output is not connected to load
Restart
--
Possible causes of this status code:
-Check L1 phase UPS output fuse
-Check L1 phase output switch LEG
-Check the SLAVE UPS L1 phase output terminal for bad
connection
- Check the SLAVE UPS L1 phase output cable to load L1 phase
- Call service
832 Status code
Status
Inverter warning
Description
SLAVE UPS L2 phase output is not connected to load
Restart
--
831 Status code causes are valid for L2 phase
833 Status code
Status
Inverter warning
Description
SLAVE UPS L3 phase output is not connected to load
Restart
--
831 Status code causes are valid for L3 phase
841 Status code
Status
Inverter warning
Description
MASTER UPS L1 phase output is not connected to load
Restart
--
Possible causes of this status code:
-Check L1 phase UPS output fuse
-Check L1 phase output switch LEG
-Check the SLAVE UPS L1 phase output terminal for bad
connection
-Check the SLAVE UPS L1 phase output cable to load L1 phase
-Call service
Summary of Contents for DS300SHPA Series
Page 1: ...DS300SHPA SERIES DSP Controlled UPS pf 0 8 10 15 20 30 kVA 3 Phase IN 3 Phase OUT USER MANUAL...
Page 2: ......
Page 17: ...15 Figure 2 3 External Battery Connections 60x12V 30x12V Batteries 30x12V Batteries...
Page 18: ...16 Figure 2 3a DS300SHPA Series 10 15 20 KVA Internal Battery Connections 60x12V 5Ah...
Page 19: ...17 Figure 2 3a DS300SHPA Series 10 15 20 KVA Internal Battery Connections 60x12V 7 9Ah...
Page 70: ......
Page 71: ...AGKK13761 10 2021...