3.4 STATUS CODES
Inverter module status codes
INV L1-L2-L3 phase status codes
163
During soft start at the end of 4 seconds L1 output voltage is less then 30 volts AC
263
During soft start at the end of 4 seconds L2 output voltage is less then 30 volts AC
363
During soft start at the end of 4 seconds L3 output voltage is less then 30 volts AC
164
During soft start at the end of 4 seconds L1 output voltage is bigger then (output high/2) value
264
During soft start at the end of 4 seconds L2 output voltage is bigger then (output high/2) value
364
During soft start at the end of 4 seconds L3 output voltage is bigger then (output high/2) value
165
During inverter run the L1 phase AC output voltage is bigger then output high alarm level
265
During inverter run the L2 phase AC output voltage is bigger then output high alarm level
365
During inverter run the L3 phase AC output voltage is bigger then output high alarm level
166
During inverter run the L1 phase AC output voltage is less then output low alarm level
266
During inverter run the L2 phase AC output voltage is less then output low alarm level
366
During inverter run the L3 phase AC output voltage is less then output low alarm level
167
L1 phase by-pass SCR must be off but at there is AC voltage at the L1 output of the UPS
267
L2 phase by-pass SCR must be off but at there is AC voltage at the L2 output of the UPS
367
L3 phase by-pass SCR must be off but at there is AC voltage at the L3 output of the UPS
168
L1 phase overload shutdown
268
L2 phase overload shutdown
368
L3 phase overload shutdown
169
Overcurrent occured on L1 phase longer then allowed time
269
Overcurrent occured on L2 phase longer then allowed time
369
Overcurrent occured on L3 phase longer then allowed time
170
On L1 phase momentary short circuit conditions occured but now inverter is running
270
On L2 phase momentary short circuit conditions occured but now inverter is running
370
On L3 phase momentary short circuit conditions occured but now inverter is running
171
On L1 phase output short circuit occured output shutdown
271
On L2 phase output short circuit occured output shutdown
371
On L3 phase output short circuit occured output shutdown
172
Within time window 4 times L1 phase output is less then output low alarm level
272
Within time window 4 times L2 phase output is less then output low alarm level
372
Within time window 4 times L3 phase output is less then output low alarm level
173
Within time window 4 times L1 phase output is higher then output high alarm level
273
Within time window 4 times L2 phase output is higher then output high alarm level
373
Within time window 4 times L3 phase output is higher then output high alarm level
174
On L1 phase UPS output at last 100 milliseconds the alternance don't changed
274
On L2 phase UPS output at last 100 milliseconds the alternance don't changed
374
On L3 phase UPS output at last 100 milliseconds the alternance don't changed
175
On L1 bypass input phase at last 100 milliseconds the alternance don't changed
275
On L2 bypass input phase at last 100 milliseconds the alternance don't changed
375
On L3 bypass input phase at last 100 milliseconds the alternance don't changed
176
On L1 inverter output phase at last 100 milliseconds the alternance don't changed
276
On L2 inverter output phase at last 100 milliseconds the alternance don't changed
376
On L3 inverter output phase at last 100 milliseconds the alternance don't changed
177
L1 phase output current sensor open
277
L2 phase output current sensor open
377
L3 phase output current sensor open
Summary of Contents for DS300SHA Series
Page 1: ...DS300SHA SERIES DSP Controlled UPS Pf 0 8 10 15 20 30 kVA 3 Phase IN 3 Phase OUT USER MANUAL ...
Page 2: ......
Page 17: ...14 Figure 2 3 External Battery Connections 60x12V 30x12V Batteries 30x12V Batteries ...
Page 18: ...15 Figure 2 3a DS300SHA Series 10 15 20 30 KVA Internal Battery Connections 60x12V 5Ah ...
Page 19: ...16 Figure 2 3a DS300SHA Series 10 15 20 30 KVA Internal Battery Connections 60x12V 7 9Ah ...
Page 56: ......
Page 57: ...AGKK12611 10 2021 ...