9
1.4 Technical Specifications
MODEL
DS3100A
DS3120A
DS3160A
DS3200A
Output (KVA)
100 kVA
120 kVA
160 kVA
200 kVA
Output (KW)
80 kW
96 kW
128 kW
160 kW
Output Power Factor
0,8
INPUT
Number of Phases
3 Phase + Neutral
Input Voltage
220/380, 230/400 or 240/415 Vac
Input Voltage Tolerance
+20% , -25% (+15% at 240/415Vac)
Input Power Factor (PF)
0,98 - 0,99 (at full load)
Input THDI
<= 5% (at full load)
Input Frequency
50/60 Hz.
±
10%
By-pass Voltage
220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
By-pass Frequency
50 Hz.
±
2%
RFI Level
EN62040-2
OUTPUT
Number of Phases
3 Phase + Neutral
Output Voltage
220/380, 230/400 or 240/415 Vac
Output Voltage Tolerance
±
1%
Output Frequency
50/60 Hz
Output Frequency Tolerance (Synchronous)
±
2%
Output Frequency Tolerance (Battery)
±
0,1% (free/battery operation mode)
Efficiency (100% Load)
up to 94%
Load Crest Factor
3:1
Output Voltage THD (linear load)
<=2%
Overload
125% Load 10min. , 150% Load 1min.
BATTERY
Total Number
60 blocks 12V (2x30 serial 60 batteries, external)
Float Charge Voltage (25
0
C)
±
405V DC
End of Discharge Voltage
±
300V DC
Battery Test
Automatic and Manual
Boost Charge
Available
COMMUNICATION INTERFACES
RS232 Com Port
2 each standard (COM1 and COM2)
External Temperature Measurement Input
Available (standard)
RS485 Comm. Port
Optional
Remote Monitoring Panel
Optional
SNMP Adapter
Optional
Modbus Adapter
Optional
Alarm Relay Contacts
4 each dry contacts (function programmable) 8 optional
Digital Inputs
2 each optional
Emergency Power-Off Input
Available (standard)
ENVIRONMENT
Operating Temperature
0 – 40
0
C
Operating Humidity
<= %90 (non-condensing)
Acoustic Noise
< 68 dB
Dimensions (WxDxH) (mm)
515 x 855 x 1450
Device Type and Protection Class
Class 1 – IP20
Weight (app. kgs)
216
230
258