4
Basic Features:
•
PWM and IGBT technology
•
Pure sinusoidal output wave form and true on-line topology
•
High input power factor (IGBT rectifier), Input current limiting
•
Low input current THD (IGBT rectifier)
•
Low output voltage THD
•
High AC/AC and DC/AC efficiency (up to 94%)
•
3 separate DSP (Digital Signal Processor) control
•
Cold-start feature
•
Static By-Pass feature: Provides uninterruptable transfer to bypass source in case of
overload or UPS fault.
•
Maintenance bypass switch and warning system, by-pass short circuit protection
•
Generator operation sense input
•
LCD alphanumeric display panel providing battery, load, voltage, power and status
information in detail to user
•
Improved diagnostics and correct fault information
•
Up to 500 event memory record system (15000 alarms or warnings total)
•
Real time clock and calendar system
•
Overload operation 10 minutes at 100% - 125% load, 1 minute at 125% - 150% load
•
Output overload, over-current and short circuit protection, output current limiting
•
Reliable operation at even 100% unbalanced load condition
•
Non-linear load supply feature (CF 3:1)
•
Double polarity battery (with common terminal)
•
Automatic and manual battery test
•
3 separate maintenance clock counters
•
Battery charge with current limiting
•
Automatic and manual boost charge feature
•
Battery deep discharge protection
•
Temperature protection with 3 separate sensors
•
Interactive communication
•
Diagnostic and settings with PC ability
•
One RS232 communication port
•
3 dry contact alarm relay outputs as standard (2 optional relay outputs)
•
Improved remote monitoring panel system (optional)
•
RS232 port multiplexer (optional)
•
Direct network connection with optional SNMP support
•
MODBUS Adapter (optional)
•
Communication via Windows based T-MON software and remote monitoring and control of
UPS via modem
•
Optional softwares compatible for most computer platforms
•
Ability for labeling of UPSs by users
•
Emergency power-off support
•
Conformity to international and local standards
•
AC input and output filters
•
CE compliance
•
Input, bypass phase order protection
•
Enhanced accessory options
•
100.000 hours MTBF
•
2 years system warranty
•
10 years spare parts warranty
•
Apple mobile device application for remote monitoring
•
Small footprint area
Summary of Contents for DS POWER SH
Page 1: ...DS300SH SERIES DSP Controlled UPS 10 15 20 kVA 3 Phase IN 3 Phase OUT USER MANUAL...
Page 2: ......
Page 17: ...14 Figure 2 3 External Battery Connections 60x12V 30x12V Batteries 30x12V Batteries...
Page 18: ...15 Figure 2 3a DS300SH Series 10 15 20 KVA Internal Battery Connections 60x12V 5Ah...
Page 19: ...16 Figure 2 3a DS300SH Series 10 15 20 KVA Internal Battery Connections 60x12V 7 9Ah...
Page 56: ......
Page 57: ...AGKK11460 04 2015...