42
SERVICING
Installation and Servicing
1.
Refer to Frame 42.
2.
Pull off the rubber pipe at the sump drain.
3.
Disconnect the condensate drain pipe.
4.
Turn the siphon clockwise to disengage
and lift to remove.
Note.
Keep siphon upright when removing.
5.
Clean siphon with water or replaced if
damaged.
6.
Re-assemble in reverse order.
7.
When re-assembling ensure the trap is
full of water.
8.
Check operation of the boiler. Refer to
Frames 31 & 32.
52 CONDENSATE TRAP/SIPHON REPLACEMENT
3
51 DIVERTER VALVE ACTUATOR REPLACEMENT
Refer to Frame 39.
To remove the motor:
1. Remove the condensate trap/siphon. Refer to
Frame 39.
2. Place a flat bladed screwdriver in the actuator slot
provided and ease out the actuator.
3. Before replacing the diverter valve actuator proceed
as follows:
a. Ensure that the switched live to the boiler is off
and that all DHW taps are shut and that pre-
heat is switched off.
b. Press and hold the “PREHEAT” and “RESTART”
buttons together for more than 5s, the last 3
faults will then be shown in sequence before
“SL” is shown
c. Press “PREHEAT”, “SH” will be shown
d. Press “PREHEAT”, “UF” will be shown
e. Press “PREHEAT”, “DU” will be shown
f. Press “RESTART” and the diverter valve will
move to the mid-position
4. Disconnect the electrical plug from the motor.
Fit the new motor ensuring the arm is correctly
engaged in the metal fork and re-assemble in
reverse order ensuring the condensate trap/siphon
is refilled with water.
5. Check the operation of the boiler. Refer to Frames
31 & 32.
Note.
All spares will be delivered in mid-position
therefore ignore point 3 and proceed to point 4.
1
Siphon
3
6
SER
VICING