Hysteresis of the external floor sensor – additional information:

the limit of a temperature value measured by the external floor sensor is of 28 °C for the factory setting 

of the advanced options and the factory value of the external floor sensor hysteresis is of 2 °C. When the 

temperature rises to 28 °C, the thermostat stops supplying the controlled heating device and reminds 

you of the high temperature alarm. If the temperature measured by the external floor sensor decreases 

to 26 °C, the thermostat will start supplying the controlled heating device again (only if the air temperatu

-

re in the room is lower than the set temperature). The thermostat will not supply power to the controlled 

heating device until the error has been corrected!

INSTALLATION OF THE EXTERNAL SENSOR

Place the protective conduit in the groove in the floor with the sensor inside. The end of the protective 

conductor must be sealed. The sensor wire can be extended up to 50 meters with other wires, if neces

-

sary. If a multi-core cable is used for the extension, it must not be used for power supply (e.g., for the 

heating cable) in order to avoid interference of the voltage signal with the heating signal of the thermo

-

stat. The resistance of the NTC sensor must be measured.

The resistance of the NTC sensor is measured with a universal meter set to measure resistance in the 

range from 20 kΩ. The measurement of the floor sensor resistance is of control and informational natu

-

re, and its purpose is, similarly to the measurement of the heating system resistance, to exclude damage 

of the connection wire (e.g., its tearing when pulling it into the conduit) or the NTC sensor itself. Approxi

-

mate resistance values, depending on the temperature of the installation base, are given in the following 

table. Tolerance of the measured value is +/– 10%.

      

INFORMATION:

It is forbidden to connect a heating device which nomi

-

nal  output  power  exceeds  3600W  to  the  thermoregu

-

lator.  Exceeding  this  value  may  cause  damage  to  the 

thermoregulator or even fire in the over-loaded system. 

Connection of a heating device with power greater than 

3600W requires the use of a contactor. Correct configu

-

ration and operation of the thermoregulator is obligato

-

ry condition to be able to make use of the statutory war

-

ranty and warranty rights granted by the manufacturer 

of the thermoregulator.

Temperature of installation surface 

 

°C

Resistance

 

5

22

10

18

15

15

20

12

25

10

www.termofol.pl

[email protected]

+48 (12) 376 86 00

DISCOVER OUR OTHER PRODUCT:

TERMOFOL TF-WIFI Mark II

TERMOFOL TF-H6 WIFI

Installation manual 

 

in different languages

ERROR CODES DISPLAYED BY THE THERMOSTAT

The  correct  configuration  of  the  built-in  and  external  floor  temperature  sensor  must  be  selected  in 

advanced settings (SEN). Incorrect selection or a sensor failure (malfunction) will cause an error messa

-

ge to appear on the screen. Displaying ‘Er’ indicates a malfunction of the external temperature sensor. 

The thermostat will not supply power to the controlled heating device until the error has been corrected!

PLACE OF INSTALLATION

FITTER’S DETAILS

Name of com

-

pany

Forename 

and surname

Address 

(street, no.)

Postal 

code

Locality

NIP

Tel.

WARRANTY CARD

Date

Fitter’s signature

Fitter’s stamp

Summary of Contents for Mark II TF-H2

Page 1: ...SEN Rodzaj czujników 0 tylko wewnętrzny czujnik temp wł 1 tylko zewnętrzny czujnik temp wł 2 włączony wewnętrzny i zewn czuj nik temperatury 2 2 OSU Ograniczenie maksymalnej temp czujnika zewnętrz nego 5 99 C 28 C 3 dlF Histereza zewnętrznego czujnika temperatury 1 9 C 2 C 4 SUH Maksymalna wartość pro gramowanej temp 5 99 C 35 C 5 SUL Minimalna wartość progra mowanej temperatury 5 99 C 5 C 6 AdJ K...

Page 2: ... sygnałem ogrzewania termostatu Należy wykonać pomiar rezystancji czujnika NTC Pomiar rezystancji czujnika NTC przeprowadzamy miernikiem uniwersalnym ustawionym na pomiar rezystancji w zakresie od 20 kΩ Pomiar rezystancji czujnika podłogowego ma charakter kontrolno informacyjny i ma na celu po dobnie jak pomiar rezystancji systemu grzewczego wykluczyć uszkodzenie przewodu przyłączeniowego np jego ...

Page 3: ...ance with the next section of this manual CONTROLLING DESCRIPTION OF THE FUNCTIONS OF THECONTROL BUTTONS DISPLAY ICONS SPECIFICATION No Symbol Setting item Parameter setting function Factory default 1 SEN Sensor control option 0 internal sensor 1 external sensor 2 internal control temperature and external limit temperature 2 2 OSU Limit temperature value of external sensor 5 99 C 28 C 3 dlF Return...

Page 4: ...f the heating system resistance to exclude damage of the connection wire e g its tearing when pulling it into the conduit or the NTC sensor itself Approxi mate resistance values depending on the temperature of the installation base are given in the following table Tolerance of the measured value is 10 INFORMATION It is forbidden to connect a heating device which nomi nal output power exceeds 3600W...

Reviews: