PROBLEM SOLVING

Problem

Possible cause

Solution

Device is plugged in, LCD 

display is empty.

Problem with the con-

nection.

Check the power wire 

connection, plug and the 

socket.

Device does not heat, E7 

or E9 is flashing on the 

display panel.

Device signals emergency, 

temperature sensor has 

been damaged.

Disconnect the device 

completely and wait until 

the radiator cools down, 

after that reconnect the 

device. 

Controller has been incor-

rectly installed on the 

heating element. 

Check if the heating ele-

ment head is hidden com-

pletely. Turn the screw 

off, press the controller 

towards the radiator and 

twist the screw again. 

Device does not heat, E6 is 

flashing on the LCD panel.

Device signals emergency, 

overheating.

Check if the radiator is 

properly filled with the 

heating agent.

Device is heating although 

it has been turned off with 

the   button.

Electronics damage.

Disconnect the device 

completely and wait until 

the radiator cools down, 

after that reconnect the 

device.

If the problem persists, please contact your local distributor.

KTX 4

 button – turns the device on / off 

 button – TIMER programming

Buttons   and   – temperature regulation or modification of TIMER settings – numeric 

sign

 icon – HEATING indicator

 icon – icon indicating connection to a transmitter

Heating element unit heats the radiator that it is installed in and precisely controls its 

temperature at the same time. Buttons   and   are used to regulate temperature whilst 

the   icon indicates that the radiator is being preheated.

Turning the device on does not mean that it uses the same maximum power for the

whole time it is on. On turning the device on, it operates with the nominal power for

a short period of time in order to heat up the radiator to the set temperature. After

that it turns itself on and off periodically, using only as much energy as it is required

to maintain the set temperature of the radiator for current external conditions (see: 

Actual working time meter

).

Construction of the heating element unit as well as physical characteristics of the heating 

agent cause that the bottom pipes (especially the two at the very bottom of the radiator) 

may have a lower temperature than the remaining parts of the radiator – this is a normal 

phenomenon. 

KTX 4 controller installed on the SPLIT heating element is the basic configuration of this 

type of heating element unit which allows use of all the basic features of the device (see: 

Local mode operation

).

KTX 4 controller can also cooperate with an external wall-mounted transmitter (ie. DT-IR 

type), which adds additional features to the basic set (see: 

Remote mode operation

).

Summary of Contents for KTX 1

Page 1: ...tric Heating KTX 1 KTX 2 KTX 3 KTX 4 Gebrauchsanweisung Elektroheizpatrone KTX 1 KTX 2 KTX 3 KTX 4 Mode d emploi Kit r sistance lectrique KTX 1 KTX 2 KTX 3 KTX 4 N vod na obsluhu Topn t leso KTX 1 KTX...

Page 2: ...not open the casing 9 Heating element s electric output cannot exceed 100 heating output of the radiator for the following parameters 75 65 20 C 10 Pressure inside the radiator must not exceed the pre...

Page 3: ...off switch Electric supply 230 V 50 Hz Heating output available 120 200 300 400 600 800 1000 W Device protection class Class I Radiator connection G 1 2 Casing protection mark IPx4 for MS IPx5 for PB...

Page 4: ...he below instructions 4 Other methods of correct filling of radiator can be found on www termaheat pl Radiator should not be filled with a heating agent of temperature higher than 65 C 5 Heating eleme...

Page 5: ...troller to be flooded or wetted 13 When the level of the heating agent stops rising wait another 5 minutes turn off the heating element unit and disconnect the device from electricity 14 Do not wait u...

Page 6: ...tion and bleed it 6 Make sure that the connection between the radiator and the heating element unit is tight 7 Install the controller fit the indents on the head A with the indents in the control ler...

Page 7: ...24 MAINTENANCE 1 Disconnect the device from electricity prior to cleaning 2 Heating element control head should be cleaned with a dry or damp cloth with a very small amount of detergents which should...

Page 8: ...teristics of the heating agent cause that the bottom pipes especially the two at the very bottom of the radiator may have a lower temperature than the remaining parts of the radiator this is a normal...

Page 9: ...ile the device is on the device will turn off after 2 hours 2 TIMER Mode can also be used to TURN the device ON Turn the device off using the button press the button the device will turn on after 2 ho...

Page 10: ...turns itself on and off periodically using only as much energy as it is required to maintain the set temperature of the radiator for current external conditions ANTI FREEZE FUNCTION When the device i...

Page 11: ...to deactivate the Timer press the button for a while use the arrows to set the Timer to OF and press again the device will switch to the Manual Mode During the Timer operation Dryer Mode can also be...

Page 12: ...ator icon icon indicating connection to a transmitter Heating element unit heats the radiator that it is installed in and precisely controls its temperature at the same time Buttons and are used to re...

Page 13: ...eading Press and hold the button the display panel will show letter E followed by 4 digits separated by a hyphen actual operating time of the device ie E 0 2 1 5 means that the device was actually wor...

Page 14: ...g signal the device will automatically return to remote operation PROBLEM SOLVING Problem Possible cause Solution Device is connected to electricity LED display panel is empty Connection problem Check...

Page 15: ...e to incorrect not in accordance with the manual installation use or disassembly incorrect use of the heating element ie for any purpose that is not specified by the Manufacturer as intended for this...

Page 16: ...TERMA Sp z o o Czaple 100 80 298 Gda sk Poland tel 48 58 694 05 00 fax 48 58 694 05 06 terma termagroup pl www termagroup pl MPGKE 92...

Reviews: