Section 4 • Troubleshooting
September 2008
Part No. 134277
T70, T90 & T120 Super Quiet Generator
4 - 5
TROUBLESHOOTING
FAULT
POSSIBLE CAUSE
SOLUTION
Engine won’t crank
Engine “ON/OFF” switch
Check switch position
set in “OFF” position
Blown fuse in DC
Replace with 25 Amp.
control circuit
SLO-BLO TYPE
fuse if needed.
E-Stop
Check to see if engaged
Defective starter
Replace solenoid
solenoid
Defective starter
Replace starter
Seized engine
Have engine checked by a
qualified technician
Engine runs, but loses
Unit is overloaded
Reduce load
speed
Improper connection
Check or Call TEREX Service
Engine runs, but loses
Clogged fuel system
Check fuel system
power under load
air in fuel lines
Blocked air intake
Check air cleaner
Blocked exhaust
Check exhaust system
Contaminated fuel
Check fuel/water separator and
fuel tank for contamination
Faulty governor, defective
Have unit checked by a
injectors, or defective fuel
trained service technician
pump
for all of these items
Engine shuts down
Oil Pressure Switch
Not opening
automatically and
TROUBLE LIGHT on
Improper coolant
Use a 50/50 on
CONTROL PANEL
or water mixture
mix of water and
is illuminated
anti-freeze only