KRB-5368c
-40-
6) Raise the OCR to unlatch from other parts, remove the OCR and place it on the top of the breaker body. See Fig. 37.
7) Remove the OCR connector .
Fig. 37 Removing the OCR connector
8) Remove the relay retainer shown in Fig. 38 and remove the control relay from the relay base.
Fig. 38 Control relay and related parts
9) Reinstall each part or component in reverse order of removal after inspection.
Latch
OCR
OCR connector
Relay retainer
Control relay
Relay base