KRB-5368c
-18-
Table 11 Ratings of undervoltage trip device (UVT)
Rated voltage
(V)
Opening voltage
range (V)
Attraction voltage
(V)
Coil exciting
current (A)
Power consumption (VA)
Coil resistance (ohm) *
Normal
Attraction
AC100
35 - 70
85
0.1
8
10
Holding coil: 410 – 510
Attraction coil: 5.6-6.8
AC110
38.5 - 77
93.5
AC120
42 - 84
102
AC200
70 - 140
170
AC220
77 - 154
187
AC240
84 - 168
204
AC380
133 - 266
323
AC415
145 - 290
352
AC440
154 - 308
374
DC24
8.4-16.8
20.4
DC48
16.8-33.6
40.8
DC100
35-70
85
* Ambient temperature: 20°C
Table 12 Ratings of auxiliary switches
Voltage (V)
Auxiliary switches
For general feeder
For microload
Resistive load (A) Inductive load (A)
*1
Resistive load (A) Inductive load (A)
*2
AC100 - 250
5
5
0.1
0.1
AC251 - 500
5
5
-
-
DC30
1
1
0.1
0.1
DC125 - 250
1
1
-
-
*1: AC cosø
≥
0.3, DC L/R
≤
0.007
*2: AC cosø
≥
0.6, DC L/R
≤
0.01
*3: Min. applicable load: DC5V/1 mA
Table 13 Ratings of operation indication contacts
Voltage (V)
Rated contact current (A)
Group indication
Spring charging/tripping operation
Resistive load (A)
Inductive load (A) *1
Resistive load (A)
Inductive load (A) *2
AC250
3
3
3
3
DC30
3
3
3
2
DC125
0.5
0.25
0.5
0.5
DC250
0.3
0.15
0.1
0.1
*1: AC cosø
≥
0.3, DC L/R
≤
0.007
*2: AC cosø
≥
0.6, DC L/R
≤
0.01
*3: Min. applicable load: DC5V/1 mA
Table 14 Ratings of N-phase CT
Type of ACB
Type of N-phase CT
Ratings (A)
AR206E
T2GB40N06A
630A/100mA
AR208E
T2GB40N08A
800A/100mA
AR210E
T2GBX6N10A
1000A/100mA
AR212E
T2GBX6N12A
1250A/100mA
AR216E
T2GBX6N16A
1600A/100mA