NSVM, NSVMN

 

  

  2      

 

 

 

 

WARNING

 

 

warranty. 

WARNING

 

 

 

4.3 Minimum inlet pressure-NPSH

 

Ø

 

To avoid cavitation, make sure that there is a minimum pressure on the suction side of the pump. 

NPSHA 

(Net Positive Suction Head Available) 

--The net positive suction head available is a function of the pump 

suction system. 

NPSHR 

(Net Positive Suction Head Required) 

--The net positive suction head required is a function of the pump 

design at the operating point on the pump performance curve. 

NPSHA=Ha-Hs-Hf-Hv-Hst (in Feet head)

 

Ha: 

Barometric pressure.(That can be set to 33 ft) 

Hs: 

Suction lift. 

Hf: 

Friction loss in suction pipe. 

Hv = KT+KH: 

Vapor pressure 

KT: 

Flow resistance due to liquid temperature. 

KH: 

Flow resistance due to elevation above sea level. 

If the liquid is water, you can consult the tables to determine the 
values of 

KT 

and 

KH.

 

 

T

 

(

°

C)

 

20

 

30

 

40

 

50

 

60

 

70

 

80

 

90

 

100

 

110

 

120

 

KT

 

(ft)

 

 0.656

 

 1.312

 

 2.624

 

 4.264

 

 7.216

 

10.824

 

16.4

 

24.272

 

36.08

 

49.2

 

 72.16

 

 

H

 

(ft)

 

0

 

500

 

1,000

 

1,500

 

2,000

 

2,500

 

3,000

 

KH

 

(ft)

 

0

 

 1.804

 

 3.608

 

 5.412

 

 7.216

 

9.02

 

10.824

 

 

Hst: 

Safety margin. (minimum: 2 ft head) 

NPSH

≧ 

NPSH

R

Pump running will be fine. 

NPSH

A

 

NPSH

R

The pump will be dry running or cavitating. 

Stop operation of the pump if cavitation occurs. Cavitation will cause pump damage and the resultant damage is not subject to 

 

 

4.4 Minimum nominal flow rate

 

To prevent overheating of the internal pump components, the pump should not be used at flows below the minimum flow rate. 

Do not run the pump against a closed discharge valve for longer than a few seconds. 

The curve below shows the minimum flow rate as a percentage of the nominal flow rate in relation to the liquid temperature. 

 

4.6 Electrical data 

See the motor nameplate. 

WARNING 

Make sure that the supply voltages, phase and frequencies correspond to the motor specifications.

 

 

4.7 Number of starts per hour

 

Motors up to and including 5.5HP: Maximum 100 times per hour. 
Motors of 7.5 HP and up: Maximum 40 times per hour.

WARNING 

If you use another brand of motor then check the manufacturer’s instructions for the maximum frequency of starts.

 

 

< 

Summary of Contents for NSVM 25 Series

Page 1: ...Installation Operating Manual VERTICAL MULTI STAGE CENTRIFUGAL PUMP NSVM NSVMN...

Page 2: ......

Page 3: ...and applications 3 Applications NSVM NSVMN series in line pumps booster pumps are designed for a wide range of applications in various industries for water treatment water boosting water supply coolin...

Page 4: ...H ft 0 500 1 000 1 500 2 000 2 500 3 000 KH ft 0 1 804 3 608 5 412 7 216 9 02 10 824 Hst Safety margin minimum 2 ft head NPSHA NPSHR Pump running will be fine NPSHA NPSHR The pump will be dry running...

Page 5: ...pump follow the installation examples in order to avoid damaging the pump Pos Description 1 Pipe support Support piping system properly to avoid stresses on connections 2 On off valves Install on off...

Page 6: ...d well insulated Overload protection should be provided To connect proceed as shown on the inside of the terminal board cover The terminal box can be turned to four positions Check the direction of ro...

Page 7: ...hus making the filling procedure easier When the operation is stable the bypass valve can be closed If the pumped liquids contains air it is advisable to leave the bypass valve open if the operating p...

Page 8: ...s operating limits Check the operating conditions of the pump b The control panel is situated in an excessively heated area or is exposed to direct sunlight Protect the control panel from heat sources...

Page 9: ...ove the operating conditions of the pump suction conditions head flow resistance liquid temperature viscosity etc b Make sure that pump and motor shafts are properly aligned Adjust the pump and or mot...

Page 10: ...NSVM NSVMN 8...

Page 11: ...NSVM NSVMN 9...

Page 12: ...NSVM NSVMN 10...

Page 13: ...NSVM NSVMN 11 NSVM N 25L 25 32 Coupling adjustments...

Page 14: ...NSVM NSVMN 12 NSVM N 40 50 50B Coupling adjustments...

Page 15: ......

Page 16: ...TED Room 1001 10 F Olympia Plaza 255 King s Road North Point Hong Kong Tel 852 2571 0282 Fax 852 2571 0619 E mail sales teralasia com TERAL INC Head O ce 230 Moriwaki Miyuki cho Fukuyama city Hiroshim...

Reviews: