TCW280_R1.2 – February 2019
Page 14
6.2.3.4.
Monitoring page automatic refresh
Monitoring page refresh interval can be set between 0 and 253 seconds. Zero means no
automatic refresh.
6.2.3.5.
Display
All three sections on Monitoring page can be added/removed independently by appropriate
setup here.
6.2.4.
Time
For proper operation of schedules, there is an internal real-time clock (RTC). It can be set either
manually or automatically.
For automatic clock synchronization, the controller supports NTP (Network Time Protocol) and all
necessary parameters for automatic synchronization are available in this section.
By default NTP synchronization is disabled, server – time.google.com, Time zone +00:00 and
interval of 12 hours.
It is strongly recommended to use time.google.com as a time server.