OPIS
Status LED indicator
DESCRIPTION
Test funkcionalnosti ili test kapaciteta
baterija je u tijeku
Function or Capacity test ongoing
Greška LED izvora (kratki spoj, prazni hod…)
Lamp failure (short circuit, open loop)
Greška baterije (napon, kapacitet)
Battery failure (Voltage, Capacity)
Baterijski rad je deaktiviran
Emergency Mode deactivated (Inhibit
Mode)
Mrežni rad, punjenje
Normal Mode, Charging
Svaka točkica označava vrijeme od 256ms / Every dot correspond to 256 ms of time
Razlozi nefunkcionalnosti mogu biti slijedeći (po vjerojatnosti
događanja):
- baterije su prazne. Treba ostaviti svjetiljku na mrežnom napajanju.
Nakon nekog vremena signalizacija će sama preći u zeleni LED
trepteće svjetlo i nužna rasvjeta će postati funkcionalna,
- centralna blokadna sklopka nije adekvatno zategnuta – svjetiljka
je u beznaponskom stanju. Treba adekvatno zategnuti centralnu
blokadnu sklopku i signalizacija će sama preći u zeleni LED
trepteće svjetlo i nužna rasvjeta će postati funkcionalna,
- električki priključak je izveden pogrešno. Priključak treba izvršiti
prema shemi spajanja,
- baterije su stare, trajno se pune nazivnom strujom punjena i
pregrijavaju se. Potrebno je zamijeniti baterijski modul BATEx 02,
- baterije su stare i ne mogu dosegnuti potreban napon punjenja i
kapacitet. Potrebno je zamijeniti baterijski modul BATEx 02,
- temperatura okoline je izvan danih granica.
Samonadzor ne uključuje kontrolu ispravnosti LED-a.
Opis oznake na svjetiljci
,
sukladno EN 60598-2-22:2014:
X - sigurnosna svjetiljka s baterijama ugrađenim u svjetiljku,
1 - sigurnosna svjetiljka u trajnom spoju,
A - sigurnosna svjetiljka sa samonadzorom i signalizacijom stanja,
B - sigurnosna svjetiljka s mogućnosti rada na mreži i automatskog
uključenja nakon povrata napajanja,
C - sigurnosna svjetiljka s Remote switch funkcijom,
D - sigurnosna svjetiljka za prostore s posebnim opasnostima,
180 - sigurnosna svjetiljka s autonomijom max. 3h.
Reasons for this may include some of the following (the probability
of events):
- batteries are empty. The lamp should be left on the power supply.
After a while the signalization will by itself transfer into green LED,
blinking lights and emergency lighting will become functional,
- central interlocking switch is not adequately tightened – light fitting
is in non load condition. It should adequately tightened central
interlocking switch and blinking lights and emergency lighting
becomes functional,
- connection is made incorrectly. Connection should be made
according to the connection scheme
- batteries are old, permanently charged with rated current and are
overheating. It is necessary to replace the battery module BATEx 02
- batteries are old and can't reach the required charging voltage and
capacity. It is necessary to replace the battery module BATEx 02,
- ambient temperature is outside specification limits.
Self-monitoring does not include a control of the LEDs validity.
Description of tag on the light fitting
, according
to EN 60598-2-22:2014:
X - emergency light fitting with built-in batteries
1 - emergency light fitting in a permanent connection
A - emergency light fitting with self-monitoring and status signalling
function
B - Emergency light fitting with main power supply option and
automatically turn ON after power return option
C - emergency light fitting with Remote switch function
D - emergency light fitting for use in areas with special hazards
180 - emergency light fitting with autonomy of max. 3h.
7. DIMENZIJE
7. DIMENSIONS
X 1 ABCD 180
X 1 ABCD 180
L1 [mm]
L2 [mm]
PSF 28 LED-E
750
400
PSF 52 LED-E
1370
800